9.3 Miscellaneous faults
Fault
Cause
Solution
Position skips
by the measuring
system
Strong vibrations
Vibrations, impacts and shocks, e.g. on presses, are
dampened with so-called "shock modules". If the error
occurs
repeatedly
despite
these
measures,
the
measuring system must be replaced.
Electrical faults
EMC
Isolated flanges made of plastic may help against
electrical faults, as well as cables with twisted pair wires
for data and supply. The shielding and line routing must
be executed in accordance with the Equipment Mounting
Directives for the respective field bus system.
Extreme axial and
radial load on the
shaft may result in a
scanning defect.
Couplings prevent mechanical stress on the shaft. If the
error still occurs despite these measures, the measuring
system must be replaced.