Page 121 of 167
6.3.3.7 Write protection
PNU 65005 (control) / PNU 971 (save)
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
parameter control
PNU 65005
bit 5, see page 137.
Selection
Value Description
Default
Writable
0
Write access for parameters
PNU 65005 and PNU 971
X
Write-protected
1
Parameters
PNU 65005 and PNU 971 (parameter save) are
read-only
6.3.3.8 Write protection
PNU 972
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
parameter control
PNU 65005
bit 6, see page 137.
Selection
Value Description
Default
Writable
0
Write access for parameter
PNU 972 (device RESET)
X
Write-protected
1
Parameter
PNU 972 is read-only
6.3.3.9 Code Sequence
Alternatively, this parameter can also be set during operation via acyclic parameter access to the
function control
PNU 65004
bit 0, see page 136.
Selection
Value Description
Default
Rising
0
Rising position values,
when the magnet is moved to the end of the bar
X
Decreasing
1
Falling position values,
when the magnet is moved to the end of the bar