4.5 Setting the Node-ID and Baud rate by means of LMT services
4.5.1 Configuration of the Node-ID, sequence
Assumption:
-
LMT or LSS services enabled by means of the switches
-
LMT address unknown
-
only one LMT slave should be in the network
-
the Node-ID 12 dec. shall be adjusted
Procedure:
Perform service 04
Switch mode global protocol
,
Mode = 1, to switch the LMT slave into
Configuration Mode
.
Perform service 17
Configure NMT-address protocol
, Node-ID = 12.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
Perform service 23
Store configuration protocol
.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
--> LMT slave is reset and is in condition
PRE-OPERATIONAL
.
4.5.2 Configuration of the Baud rate, sequence
Assumption:
-
LMT or LSS services enabled by means of the switches
-
LMT address unknown
-
only one LMT slave should be in the network
-
the Baud rate 125 kbit/s shall be adjusted
Procedure:
Perform service 04
Switch mode global protocol
,
Mode = 1, to switch the LMT slave into
Configuration Mode
.
Perform service 19
Configure bit timing parameters protocol
,
Table Selector = 0, Table Index = 4
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
Perform service 23
Store configuration protocol
.
--> Wait for acknowledgement and check successfully execution,
--> Error Code = 0.
--> LMT slave is reset and is in condition
PRE-OPERATIONAL
.