Parameterization via TRWinProg
Printed in the Federal Republic of Germany
TR-Electronic GmbH 2012, All Rights Reserved
11/15/2012
TR - ECE - BA - DGB - 0091 - 02
Page 67 of 68
8.3.5 Positions Analog and Analog values in combination
The parameters specified under chapter “
Analog value at start position / end position
” are used
usually into combination with each other. In the following the relations of these
parameters are represented.
Figure 13: Positions / Analog values in combination, rotation = CW; counting direction = increasing
Legend
A
O
= Analog output quantity in Volt or Milli-Ampere
A
max
= maximum value of the analog output quantity [V, mA]
ML
= by the scaling parameters programmed measuring length in steps
Pos
= actual position of the measuring system in steps
Start-Pos.
= Start position analog in steps
End-Pos.
= End position analog in steps
Start value = Analog value at start position [mV,
µ
A]
End value
= Analog value at end position [mV,
µ
A]
Pos = ( (A
O
– Start value) * (
End-Pos.
–
Start-Pos.
) ) / (End value – Start value) + Start-Pos.