8.3.3 Analog value at start position / end position
With the parameter
Analog value at start position
and
Analog value at
end position
the active analog measuring range within the limit values of
0…+10 V or 0-24 mA can be defined. The analog value at the start position must be
chosen smaller than the analog value at the end position.
Figure 9: Analog value at start position/end position, rotation = CW; counting direction = increasing
Legend
A
O
= Analog output quantity in Volt or Milli-Ampere
A
max
= maximum value of the analog output quantity [V, mA]
ML
= by the scaling parameters programmed measuring length in steps
Pos
= actual position of the measuring system in steps
Start value = Analog value at start position [mV,
µ
A], default = 0
End value
= Analog value at end position [mV,
µ
A], default = 10000 mV
Pos = ( (A
O
– Start value) * ML ) / (End value – Start value)