TYPICAL TEST RESULTS
Oxygen
3% to 6%
Carbon Monoxide
Less than 100ppm (air free)
Stack Temperature
300
°F
to 500
°F
Draft
-0.15 inH2O
Oxygen
4% to 7%
Carbon Monoxide
Less than 100ppm (air free)
Stack Temperature
325
°F
to 625
°F
Draft
-0.15 inH2O
Power Burners (Gas Fired)
Power Burners (Oil Fired)
Oxygen
7% to 9%
Carbon Monoxide
Less than 100ppm (air free)
Stack Temperature
325
°F
to 500
°F
Draft
-0.15 inH2O to -0.4 inH2O
Gas Fired Burners (Atmospheric / Fan Assist)