SIMVFD Parameter Details
Motor Parameters
0-0
Motor Nameplate Voltage
Range:
208, 230, 400, 460, 575
Default Setting:
208
This parameter determines the Maximum Output Voltage of the drive.
The Maximum Output Voltage setting must be less than or equal to the rated voltage of the motor as indicated on
the motor nameplate.
0-1
Motor Nameplate Amps
Range:
3.80, 5.12, 6.10, 13.40, 18.00, 21.00
Default Setting:
3.80
This parameter sets the output current to the motor. The value is determined by the value found on the motor nameplate.
0-2
Motor Base Frequency
Range:
50/60
Default Setting:
60
This parameter setting is determined by the motor nameplate data.
0-3
Motor Base RPM
Range:
800, 970, 1155, 1450, 1725, 2000
Default Setting:
800
This parameter setting is determined by the motor nameplate data.
0-4
Motor Maximum RPM
Range:
P0-3 to 2000 rpm
Default Setting:
P0-3
This parameter setting is determined by the needs of the application, but should not exceed the maximum RPM
rating of the motor being used.