10. Operation

                                                                       

 

 
            (1) The data frames to be sent to the receiving unit are first sent to the transmission buffer of the 

equipment from an external device.    The data in the transmission buffer is sent to the receiving 
unit at a converted rate of 2.5Mbps. 

  * Note. If a unit not supporting the flow control (IEEE802.3x) is connected in full-duplex mode, 

some data frames may be lost when data exceeding the buffer capacity (16kB) is sent at a time. 

If any data frame is lost, try to take the following actions. 

Action (1): Set both type A and B units to half-duplex mode. 

In half-duplex mode, a back pressure is applied in case of buffer overflow.    The 
sending unit is requested to transmit data again after waiting for a while. 

Action (2): Increase the interval after each transmission by the sending unit. 

Reduce the size of each data to be sent at a time to about 14kB and increase the 
interval before sending the next data. 
As a guide, the transmission intervals shall be approximately equivalent to the data 
size (in bytes) multiplied by 4µs. 

Action (3): Change the device connected with the optical transmitter to a one supporting the flow 

control to automatically increase the intervals at which data is transmitted. 
The SOT-EQ80A/B supports the flow control. 
The transmission intervals are automatically adjusted between the units in case of 
buffer overflow. 
When connecting the unit, activate the auto negotiation function. 

Action (4): Use a protocol such as TCP to retransmit the lost frames. 

 

(2) The data frames sent back from the receiving unit are sent to the reception buffer in the equipment.   

The data in the reception buffer is sent to the external device at a converted rate of 10Mbps. 

 

     

(3) Functions of sending data indicator lamp (SD) and receiving data indicator lamp (RD) 

       

  Sending data indicator lamp (SD) blinks in red when sending input is active. 

       

  Receiving data indicator lamp (RD) blinks in green when receiving input is active. 

 

     

(4)When optical path is shielded, the receive indicator lamp goes off, and no data can be   

sent any longer. Reception level is not displayed, either, at the receiving unit. 

 

     

(5)Functions of link indicator lamp (LINK) and full-duplex indicator lamp (FDX) 

Link indicator lamp (LINK) shows green when the network connection with the external device 
connected to the signal connector is normal.   
Full-duplex indicator lamp (FDX) shows green when the network connection with the external 
device connected to signal connector is in full-duplex mode. 

 

     

(6) Aux. output operates as shown below. 

       

  1) DL: Transistor turns on when the data link is normal. 

       

  2) ALM: Transistor turns off when the reception level indicator lamp (LEVEL 1) is off. 

 

     

(7) The statuses of indicators and subsidiary outputs change as shown below when the beam is received 

or interrupted. 

Summary of Contents for SOT-EQ80 Series

Page 1: ...DS4 2499D 1 Optical Transmitter SOT EQ80 Series Operation Manual TOYO ELECTRIC CORP...

Page 2: ...tions of Components 5 6 Installation 6 7 Electric Connections and Wiring 8 8 Setting Switches 10 9 Adjustment of the Optical Axis 11 10 Operation 12 11 Signal Interface 14 12 Maintenance and Inspectio...

Page 3: ...requency can be changed using a dipswitch and data can be transferred between up to two pairs of units on the same path or parallel paths without causing interferences This equipment is specified for...

Page 4: ...Shows green when received data output is on FDX Full duplex indicator lamp red Shows red in full duplex connection Own unit CD Clear data indicator lamp red Shows red at a sufficient reception level...

Page 5: ...ator lamp RD Blinks green when the received data output is ON 8 Link indicator lamp LINK Shows green when 10BASE T link is established 9 Full duplex indicator lamp FDX Shows green when 10BASE T link i...

Page 6: ...e near a magnet motor or other devices that generate a strong magnetic field or an inverter or another devices or electric wire that generate a strong noise 5 A place where the sunlight or candescent...

Page 7: ...n normally communicate throughout the communication area after adjustment of the optical axis according to section 9 Adjustment of the Optical Axis Example 1 Type A Type A Type B Type B 0 5 m or more...

Page 8: ...t connected 8 Transmission output and reception input may be exchanged according to the connected cable AutoMDIX function Polarity of reception input may be exchanged according to the connected signal...

Page 9: ...er or external device 2 For power supply use one conforming to the specification of this machine 3 For the load of aux output connect one within the output rating 30VDC 50mA of this machine When conne...

Page 10: ...ems so that the communication mode of Full duplex Half duplex may conform to the device connected in the receiving side across the optical transmitter Special care must be taken when connecting to the...

Page 11: ...or more First adjust by referring to the display of reception level on the receiving unit 3 Make further fine adjustment until the reception level indicator lamps on the receiving unit show green up t...

Page 12: ...tervals are automatically adjusted between the units in case of buffer overflow When connecting the unit activate the auto negotiation function Action 4 Use a protocol such as TCP to retransmit the lo...

Page 13: ...ity cleaning or beam adjustment required CD only CD or more ON OFF The same with 1 Interrupted cleaning or beam adjustment required Off Off OFF OFF Off CD or more Off OFF OFF CD or more Affected by ex...

Page 14: ...within 100 m Note 2 For power wire use electric wire of 0 3 mm2 or more Extension of power wire shall be within 50 m if power voltage is 24VDC Note 3 Voltage between DL COM or ALM COM shall be 30VDC o...

Page 15: ...wer to the equipment Data cannot be transferred for further 2 sec or so because of auto negotiation when such auto negotiation is effective 3 Optical axis adjustments Do not fail to adjust optical axi...

Page 16: ...4 Ethernet connector 1 RJ45 Clear data indicator lamp receiving unit 5 CD LEVEL1 4 Mounting seat 1 Communication indicator lamp 4 SD RD LINK FDX Channel indication limp 1 CH Mounting fixture 2 ABS res...

Page 17: ...e Machinery Division Kamiya Factory TOYO ELECTRIC CORP Electric Machinery Div Head Office Hikisawa 1 39 Kamiya cho Kasugai Aichi Japan 480 0393 Kamiya Plant TEL 0568 88 1181 FAX 0568 88 3086 Tokyo Off...

Page 18: ...tion of consumption current correction of pin arrangement of aux Output Development 2007 04 06 A power supply an assistance output connector model change address change Development 2007 11 28 Change C...

Reviews: