NON-PROGRAMMABLE

 

DIGITAL THERMOSTAT 

 

 

 

 

 

 

 

 

 

 

 

TST-EGND06413SCS09 / TST-EGND06413SCS10 

TST-EGND06423SCS09 / TST-EGND06423SCS10 

-Cool, Heat and Ventilation 

-Large, Easy To Read Display 

-Blue Backlight 

-Fahrenheit or Centigrade 

-Auto Recovery 

-2-pipe or 4-pipe Selection 

-DA or DB Type Selection 

-Key Card Function 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Specification 

Set-Point Range: 5

-35

(41

-95

Operating difference: 

±

 1

 

Switch current rating: 

<

 2A 

Sensing element : NTC   

Display: LCD 

Power supply:   

TST-EGND06413SCS09: AC85V~260V 50Hz/60Hz 

TST-EGND06413SCS10: AC85V~260V 50Hz/60Hz 

TST-EGND06423SCS09: AC24V 

±

10% 50Hz/60Hz 

TST-EGND06423SCS10: AC24V 

±

10% 50Hz/60Hz 

Dimensions: 86 × 86 × 29.5 mm (W

×

H

×

D) 

Housing: ABS Flame Retardant 

Basic Operation 

Power ON/OFF 

"

 

To turn the thermostat on, press “

”. Mode symbol (

 

or 

), 

“RT”, and room temperature will be displayed

.  

"

 To turn the thermostat off, press “

” again. There is no any display 

on LCD and no any output. 

Select Mode 

"

 Cool Setting: Press “M”, until the “

” is displayed, it will be 

confirmed automatically after 6 seconds. 

"

 Heat Setting: Press “M”, until the “

” is displayed, it will be 

confirmed automatically after 6 seconds. 

"

 Ventilation Setting: Press “M”, until the “

” is displayed, it will be 

confirmed automatically after 6 seconds. 

Fan Setting 

"

 Fan speed select: press the fan button to select “

Hi

Med

Low

Auto

”. In mode “

Auto

”, the fan-speed changed 

automatically. Auto LOW-speed When the difference between 

room-temperature and setting-temperature exceed 1

(2

), Auto 

MED-speed When exceed 2

(4

), Auto HI-speed When exceed 3

(6

). 

Setting Temperature 

"

 To enter the configuration mode: press ”

5

” or ”

6

” buttons , The “

” 

and “SET” will appear on the display. 

"

 Press”

5

” or ”

6

” to adjust the Cool Temperature. 

"

 Press ”M” button once. The “

” and “SET” will appear on the 

display. 

"

 Press ”

5

” or ”

6

” to adjust the Heat Temperature. 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Key Card Function   

TST-EGND06413SCS09 / TST-EGND06423SCS09: 

"

 If the card was removed, The thermostats will set to 26

 automatically 

in Cooling Mode and 18

 in Heating Mode; Fan will run in speed of low 

under all of the modes. 

TST-EGND06413SCS10 / TST-EGND06423SCS10: 

"

 If the card was removed, The thermostats will switch OFF 

Error Codes 

E1

 — If the thermostat cannot properly read room temperature, and it 

needs to be adjusted, E1 will be displayed. 

Set Thermostat Configuration 

Configuration options are intended to be selected at installation and 

normally should not be modified by the home owner. These options are 

not discussed in the Homeowner’s Guide and therefore must be made as 

part of the installation. A special procedure allows entry in to the 

configuration mode. The thermostat will automatically exit this if no button 

is pressed for 90 seconds.   

An explanation for each of these and how to enter the configuration mode 

follows. 

To enter the configuration mode: 

Turn off the thermostat hold the fan button down for approximately 15 

seconds. After 15 the second periof, Option”01” will appear in the display.

OPTION 01–LOW TEMPERATURE PROTECTION (FROST PROTECTION) 

In the low temperature protection mode, When the thermostat is off , and 

the room temperature is lower than 5

, it will be turned on automatically 

and in heating mode; When the room temperature is higher than 7

, it will 

be turned off automatically. 

TO ADJUST: 

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 01.The SET icon should be off.

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 01 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 01 

choices of 00(disable) or 01(enable). Factory default is 00. 

Press ”M” button again to return to Option 01. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press” 

 “button 

to exit configuration mode. 

OPTION 02 –FAHRENHEIT/CELSIUS SELECTION 

This option selects Fahrenheit or Celsius operation. 

TO ADJUST: 

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 02.The SET icon should be off.

Press ”M”button once. The SET icon will be come on. The display now 

shows Option 02 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 02 

choices of F (Fahrenheit) or C (Celsius). Factory default is C. 

Press ”M” button again to return to Option 02. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button to 

exit configuration mode. 

OPTION 03

ROOM TEMPERATURE OFFSET 

This option allows calibration (or deliberate miscalibration) of room 

temperature sensor. There are various reasons why the home owners 

want to adjust the displayed temperature. The selected number is the 

number of degrees, plus or minus, which will be added to the actual 

temperature. The number can range between -5 and +5. Factory default is 

0. This adjusted value will be used as actual temperature for both display 

and control action. For example, if 2 is selected, 72F actual will read 74F. 

If setpoint is 72, the room will control to an actual value of 70 which will be 

displayed and acted upon as if it were 72. The effect is that a positive 

number selection will make the room temperature lower and vice versa. 

This thermostat is factory calibrated within an accuracy of plus or minus 

1F, so this adjustment will provide the best accuracy when set to 0. 

TO ADJUST: 

Enter configuration mode(if not already there). 

Use “

5

” and “

6

” buttons to display Option 03.The SET icon should be off.

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 03 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 01 

choices of -5 t5 in 1 step. Factory default is 0. 

Press ”M ”button again to return to Option 03. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button to 

exit configuration mode. 

OPTION 04 –AUTO RECOVERY 

Auto recovery feature means the thermostat will retain the previous status 

when power is back. This option can be used to choose whether auto 

 

recovery feature is enabled. 

TO ADJUST:   

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 04.The SET icon should be 

off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 04 setting. 

Use “

5

” and “

6

” buttons to move between the available Option 04 

choices of 00(disable) or 01(enable). Factory default is 01. 

Press ”M” button again to return to Option 04. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button to 

exit configuration mode.

 

OPTION 06 –DA/DB TYPE SELECTION 

This option selects DA type or DB type operation. DA means that when 

temperature reaches the set point, valve will close, fan will keep running

;  

DB means that when temperature reaches the set point, Valve and fan 

will close together. 

TO ADJUST:   

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 06.The SET icon should be 

off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 06 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 06   

choices of 00 (disable) or 01(enable). Factory default is 01. 

Press ”M” button again to return to Option 06. The SET icon will now be   

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button   

to exit configuration mode. 

OPTION 07 –2-PIPE/4-PIPE SELECTION 

This option selects 2-pipe or 4-pipe operation. 

TO ADJUST: 

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 07.The SET icon should be 

off. 

Press ”M” button once. The SET icon will be come on. The display now 

shows Option 07 setting.   

Use “

5

” and “

6

” buttons to move between the available Option 07   

choices of 2 (2-pipe) or 4(4-pipe). Factory default is 2. 

Press ”M” button again to return to Option 07. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “

“ button   

to exit configuration mode. 

OPTION 08 –TYPE OF KEY CARD CONTACT 

This option selects the type of key card contact..   

TO ADJUST

 

Enter configuration mode (if not already there). 

Use “

5

” and “

6

” buttons to display Option 08.The SET icon should be   

off. 

Press” M ” button once. The SET icon will come on. The display now 

shows Option 08 setting. 

Use “

5

” and “

6

” buttons to move between the available Option 08 

choices of 00(When key card is inserted, the contact of S1 and S2 is 

open) or 01(When key card is inserted, the contact of S1 and S2 is 

closed). Factory default is 00. 

Press ” M” button again to return to Option 08. The SET icon will now be 

off. 

Use “

5

” and “

6

” buttons to select another Option, or press “ 

 “button  

to exit configuration mode.

 

 

 

 

 
 
 
 
 
 
 
 
 
 
 
 

 

 

 

 

 

2-pipe 

 

Set temperature 

 

Invalid   Fan Button  Down Button  Up Button 

Room temperature 

Cool mode  Heat mode  Ventilation 

Fan indicator 

Mode Button

 

Shows room temperature,

desired 

temperature,

 and

other feature information 
as required.

 

On/Off Button 

Wire Diagram

Thermostat

 

Fan coil 

L(R)

Val2

Val1

Low

Med

Hi 

N(C)

S1 

S2 

KEY CARD 

CONTACT

 

L(R) 

Val 

Low 

Med 

Hi 

N(C) 