RESET FILTER BUTTON — The Reset Filter button is used by the service
person to reset the Service Filter icon display.

If the Reset Filter button is pressed during normal thermostat operation,

the number of hours of fan operation is displayed.

KEYPAD LOCK — The thermostat has a keypad lockout feature which will
not acknowledge front panel buttons until the lockout sequence is entered. To
disable or lock the keypad, press and hold the Mode button. While holding
down the Mode button, press the UP and DOWN ARROW buttons simul-
taneously. The

9

Locked

9

icon will appear on the display.

The thermostat is unlocked by performing the same procedure. Press and

hold the Mode button. While holding down the Mode button, press the UP
and DOWN ARROW buttons simultaneously. The

9

Locked

9

icon will be re-

moved from the display.

OPERATION

Mode —

The Mode button selects the operating mode of the thermostat. If

OFF is selected, the thermostat will not enter Heating or Cooling mode. If
HEAT is selected, the thermostat will only enter Heating mode (if the room
temperature is below the heating set point). If COOL is selected, the ther-
mostat will only enter Cooling mode (if the room temperature is above the
cooling set point). If AUTO is selected, the thermostat will enter Heating or
Cooling mode based on the room temperature and the heating and cooling set
points.

Two-Stage Operation —

The second stage of heat or cool is turned on

when the first stage has been on for a minimum of 2 minutes and the tem-
perature differential from the set point is equal to or greater than the set point
plus the deadband plus 2 degrees.

Electric Heat —

When the Electric Heat option in the advanced set up is

set to ON, the thermostat will turn on the fan immediately any time there is
a heat demand. This feature should only be used on electric heating appli-
cations. Do not use with gas heat.

Dry Contact Switch/External Control —

A dry contact switch is pro-

vided to allow an external device to force the thermostat into Unoccupied
mode. When the thermostat is forced into Unoccupied mode via the dry con-
tact closure, the Unoccupied mode icon will blink each second.

7

Summary of Contents for Signature CPV210

Page 1: ... Electric Heat 7 Dry Contact Switch External Control 7 Remote Temperature Sensor 8 Outdoor Temperature Sensor 8 OWNER S MANUAL CPV210 Commercial Non Programmable Thermostat Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION R CARRIER CORPORATION 1 98 LITERATURE NUMBER P374 7...

Page 2: ...ntacts are provided for optional wiring to field supplied external out put device to control thermostat to occupied and unoccupied set points for energy savings Batteries are not required During power interruption the internal NEVERLOST memory stores thermostat configuration for an unlimited time IMPORTANT The thermostat has a security option which can be config ured by the installer to limit cert...

Page 3: ...an be displayed on the screen mode OFF HEAT COOL or AUTO fan setting FAN ON or blank override indication room temperature desired temperature service filter indicator outside temperature Occupied or Unoccupied mode with dry contact connection to external device setup indicator configuration mode lock indicator Fig 1 Thermostat Display 3 ...

Page 4: ...de pressing the UP ARROW or DOWN ARROW buttons will adjust both the heating and cooling set points Pressing the UP ARROW or DOWN ARROW buttons in cooling mode will adjust only the cooling set points Pressing the UPARROW or DOWNARROW buttons in heating mode will adjust only the heating set points The UP ARROW and DOWN AR ROW buttons are also used in programming mode OVERRIDE BUTTON The Override but...

Page 5: ...oints are adjustable with the UP ARROW and DOWN ARROW keys during override mode Thermostat Inner Panel Buttons The thermostat has inner panel but tons which are used to change the configuration of the thermostat set the mode and reset the filter The buttons are accessible from underneath the thermostat cover To access the inner panel buttons pull on the hinged ther mostat cover See Fig 3 The progr...

Page 6: ...button selects fan operation When the fan is set to FAN ON the fan will run continuously for improved air circulation NOTE When the thermostat is in Unoccupied mode the fan will run only during heating or cooling operation even if the fan is set to FAN ON this is the energy saving smart fan option When the fan is not set to FAN ON no icon displayed on thermostat screen the fan will run during heat...

Page 7: ... HEAT is selected the thermostat will only enter Heating mode if the room temperature is below the heating set point If COOL is selected the ther mostat will only enter Cooling mode if the room temperature is above the cooling set point If AUTO is selected the thermostat will enter Heating or Cooling mode based on the room temperature and the heating and cooling set points Two Stage Operation The ...

Page 8: ...emperature sensor is avail able to read the temperature from a space If a remote temperature sensor is connected the thermostat will ignore the reading of its internal sensor When the thermostat is using a reading from a remote sensor the degree symbol above the temperature reading will blink Outdoor Temperature Sensor An outdoor temperature sensor may be provided to read the outside temperature O...

Page 9: ...9 ...

Page 10: ...10 ...

Page 11: ......

Page 12: ...argest manufacturer of air conditioning heating and refrigeration products Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations REPLACEMENT COMPONENTS DIVISION R CARRIER CORPORATION 1 98 LITERATURE NUMBER P374 7SO PRINTED IN CHINA ...

Reviews: