Total Saft Tel.X-Plus Series Installation And Operating Instructions Download Page 1

Tel.X-Plus Ni-Cd Batteries 

TLX+80, 100, 150, and 180 Range 

(48VDC, 40 cells string) 

Installation and operating instructions

1

 

Safety 

 

Never allow an exposed flame or spark near the 

batteries, particularly while charging.  

 

Never smoke while performing any operation on 
the battery. 

 

Wear appropriate 

personal 

protection 

equipment (PPE), safety shoes, gloves, and eye 
protection.  Additional PPE (i.e. aprons, face 
shield) may be required in case of accidental 
ruptured module and exposed electrolyte.  

 

The electrolyte is harmful to skin and eyes. In the 
event of contact with skin or eyes, wash 
immediately with plenty of water. If eyes are 
affected, flush with water  for 15 minutes and 
obtain immediate medical attention. 

 

Remove all rings, watches, and other electrically 
conductive items before working on the battery. 

 

Use insulated tools. 

 

Avoid static electricity and take measures for 
protection against electric shocks. 

 

Discharge any possible static electricity from 
clothing and/or tools by touching an earth-
connected part "ground" before working on the 
battery. 

2

 

Important notice 

 

Only  Saft  trained and certified personnel 
should  assemble  and  install  Tel.X-Plus 
battery 

strings 

(contact 

your 

Saft 

representative).

 

 

Local regulations related to battery 
compartment ventilation (e.g. Telcordia GR-
487-CORE) should be carefully observed. Saft 
will  not be responsible for the non-
observance of these regulations. 

 

Refer to Saft's Installation and Operation 
manual for complete instructions. 

3

 

Unpacking and inspection 

Tel.X-Plus  batteries are shipped filled with 
electrolyte,  a  connection kit,  and  supportive 
documentation. 

 

Make sure all items are received by checking 
the material list included on each string 
layout sheet. 

 

Check for damage or electrolyte spillage. 
Report any abnormalities to the shipping 
company as well as to Saft. 

4

 

Storage 

Store  the batteries in standard warehouse 
conditions.

 

 

Do not stack modules. Use original packaging 
for storage. Do not stack boxes more than 3 
high.  

 

Do not store in direct sunlight or expose to 
excessive heat.  

 

Store the batteries in a temperature range of 
-20°C (-4°F) to +35°C (+95°F). 

 

Tel.X-Plus batteries may be stored for up to 
one year without special maintenance. 

 

If  fully charged,  the battery  strings should 
not be stored for more than 2 months (if long 
storage is required,  discharge the string to 
10% state of charge). 

5

 

Preparation for transportation 

 

Make use of original packing cases if 
possible. Otherwise,  protect the batteries 
from being damaged and short-circuited. 

 

Transport batteries upright and secured to 
prevent tipping. 

 

For transportation over public roads, each 
box or pallet must carry a "hazardous 
material"  label and any other indication 
required by local transport authorities  (DOT 
classification;  Batteries, Wet, Filled with 
Alkali, Class 8, UN2795, PG III). 

 

Safety Data Sheet (SDS) is provided with each 
shipment and  is  available  online  at 
www.saftbatteries.com. 

6

 

Installation 

6.1

 

General 

Tel.X-Plus  batteries are delivered filled with 
electrolyte and at 10% State of Charge (SOC).

 

 

Do not top up batteries with DI water before, 
during, or after initial installation. 

 

Charge the battery (according to chapter 6.6). 

6.2

 

Operating environment 

 

For tight spaces and to use a front accessible 
connection, make sure to install all back 
connections first, while blocks are staged 
outside. 

 

Tel.X-Plus should never be installed in a 
sealed space without ventilation. Refer to 
Table A for ventilation guidelines. 

 

To  prevent  inadvertent short circuit,  make 
sure the connector ends are insulated. 

6.3

 

Recommended tools 

The following tools will facilitate installation:

 

 

Insulated torque wrench capable of 10±1N.m 
(96 ± 9in.lbs). 

 

Insulated 10mm socket 

 

Digital Multi Meter (DMM), with an accuracy 
of +/-10mVDC. 

 

Clamp-on current meter, with an accuracy of 
±25mA. 

6.4

 

String assembly 

Battery configurations vary depending on the 
application. A battery string layout is provided 
with each string.  The step by step procedures 
may vary with application and layout. 

 

Measuring the cell Open Circuit Voltage (OCV) 
is recommended to check for normal cell 
condition (according to chapter 8). Before 
installation, measure the OCV of each battery 
cell and note the values (refer to Table B for 
record  keeping). The sum of the  individual 
cell voltages will be used to compare with the 
assembled battery string voltage. 

 

Temporarily position the battery modules in 
final position in accordance with the provided 
layout diagram.  Make sure to orient the 
positive and negative terminals correctly 
(when applicable,  place barcode bearing 
block on the (+) end of the battery string).

 

 

Use only the parts provided. 

 

Use “labels numerical” provided to identify 
each cell of the battery string. Starting with 
battery string positive end as cell number one, 
subsequently serialize the cells following the 
electrical path resulting in numbering battery 
string negative end cell as #40. 

 

Apply a light coat of No-Ox (provided) to all 
terminal connections made before and after 
applying torque. 

 

When making an electrical connection, torque 
the terminal bolts to 10±1N.m (96±9in.lbs). 

 

Install all back connections first while blocks 
are staged outside.  

 

After completing terminal connections, install 
the battery top cover(s) (If applicable). 

 

To prevent inadvertent short circuit, make 
sure the connectors’  exposed  ends  are 
insulated. 

 

The modules can then be slid into place and 
all 

front connections, back-to-front 

connections can be made. 

 

At this stage, DO NOT connect the system’s 
power cables. 

6.5

 

Connecting power 

 

Measure the battery string’s  overall voltage 
and compare this with the sum of individual 
OCV’s previously  measured in chapter 6.4. If 
the compared value shows  a discrepancy 
greater  than  1.0VDC, verify the polarity, 
position, and connection of each module. Re-
assemble if required. 

 

 If a battery needs to be connected to a live 
system, it may be necessary to pre-charge 
the battery prior to installation (to minimize 
the inrush current).  

 

Ensure the output of the rectifier is adjusted 
to 1.43VDC per cell; i.e.,  the DC bus voltage 
should be set to 

-57.2VDC

 for a 40 cell Tel.X-

Plus string. 