background image

QuickPanel jr.

QPKSxDN0000, QPKCxDE0000

GFK-2246

Installation Instructions

January 20, 2003

Note:

 The panel clamps are packed in the carton.

For easier maintenance and proper ventilation, ensure the display is
mounted away from all surrounding objects.

Precautions

 

When installing the display on a slanted panel, the slope of the panel should be within 30°
from the vertical position. If the slope is greater than 30°, provide fan cooling.

 

Ensure heat from other equipment does not interfere with the display.

 

For proper ventilation, provide 4" of clearance around the Quickpanel.

 

Ground the display to earth ground.

 

Panel thickness = (1.6mm to 5mm) 0.063in to 0.197in

30°

30°

O-RING

PANEL

Torque = 0.5~0.6Nm

FRONT

1. Install the gasket in the slot in

the faceplate.

2. Insert the display through the panel

opening. Insert the panel clamps into
the slots in the display body. Turn
screw clockwise to tighten.

or

FLAT

Units Marked UL and c-UL

Use No. 14 to 18 AWG, solid or stranded copper conductors and note the following precautions.

Suitable for use in Class I, Division 2, Groups A, B, C and D hazardous locations, or nonhazardous locations only. Power,
Input and Output (I/O) wiring must be in accordance with Class I, Division 2 wiring methods, Article 501-4(b) of the
National Electrical Code, NFPA 70 or as specified in Section 18-152 of the Canadian Electrical Code for installations within
Canada and in accordance with the authority having jurisdiction.

WARNING

: Explosion hazard - substitution of components may impair suitability for Class I, Division 2.

WARNING

: Explosion hazard - do not disconnect equipment unless power has been switched off or the area is

known to be nonhazardous.

WARNING

: Explosion hazard - when in hazardous locations, turn off power before replacing or wiring modules.

DC Power

1. MAKE SURE THE POWER IS OFF.

2. Remove the protective cover on the DC terminal strip.
3. Remove 1/4" of insulation from the supply wires and insert them
    under the terminal clanmps.

4. Tighten the clamp screws to secure the wires.
5. Replace the protective cover.

DC24V

22W

QPK-

4in(100mm)

4in(100mm)

SIDE

4i

n(

100m

m

)