WX9 ASD Installation and Operation Manual
OC
Over-Current
ASD output current
greater than the
setting.
• Defective IGBT (U, V, or W).
• ASD output to the motor is connected incorrectly. Disconnect
the motor and retry.
• ASD output phase-to-phase short.
• The ASD is starting into a spinning motor.
• Motor/machine is jammed.
• Mechanical brake is engaged while the ASD is starting or
while running.
• Acc/Dec time is too short.
• Voltage Boost setting is too high.
• Load fluctuations.
• ASD is operating at an elevated temperature.
*OH
*Over-Heat
ASD ambient temperature
excessive.
• ASD is operating at an elevated temperature.
• ASD is too close to heat-generating equipment.
• Cooling fan vent is obstructed (see
).
• Cooling fan is inoperative.
• Internal thermistor is disconnected.
OJ
Timer
Run-time counter
exceeded.
•
Type Reset
is required; select
Clear run timer
.
*OL1
*ASD Overload
Load requirement in
excess of the capability of
the ASD.
• Carrier frequency is too high.
• An excessive load.
• Acceleration time is too short.
• DC damping rate is set too high.
• Motor is starting into a spinning load after a momentary
power failure.
• ASD is improperly matched to the application.
OL2
Motor Overload
Load requirement in
excess of the capability of
the motor.
• Improper V/f setting.
• Motor is locked.
• Continuous operation at low speed.
• Startup frequency setting adjustment is required.
*
Reset ignored if active.
Table 13. WX9 ASD Alarms. (Continued)
LED Display
LCD Display
Description
Possible Causes/Troubleshooting