2

Cautions for Operation

The inspection opening shown below is necessary to clean the heat exchange element and the filter as required. If not cleaned,
they are likely to get clogged, resulting in degradation of performance.

This Energy Recovery Ventilators should be installed at the place where a larger space than the sizes shown below can be
secured for the ceiling space.

Unit: mm

Don't install it near the water-heater.

Refrain from the following duct installing works.

Do not use in bathrooms or food preparation areas etc.
If you use the unit at the place of much soot and high humidity, the filter or the heat exchange element gets clogged and disables
you to use it.

Use the Heat Exchange Ventilators in the ambient temperature of 40°C or less.
Never install the unit at the place where the flame likely reaches directly the unit. If you use it at the atmosphere of more than 40°C
for hours, it is likely to cause deterioration or deformation or damage of the resin part.

Be careful of dewing and frosting.
As shown in the figure to the right, suppose a high temp absorbing air condition A and a low
temp absorbing air condition B are plotted on the air line figure, then a high temp air A is
heat-exchanged by the unit and goes out of the saturation curve as shown by Point C. In
this case, the unit will be dewed or frosted. To avoid this, you are required to heat a low
temp air B up to B' so as to get C' below the saturation curve, before using the unit.

Never fail to make the inspection opening at the specific place on the ceiling so you can perform the constant cleaning or the
equipment checking of filter and heat exchange element.

Model No.

Ceiling Space A

Model No.

Ceiling Space A

VN-250SE

320

VN-800SE

440

VN-350SE

VN-1KSAE

VN-500SE

FY-01KZDY2B

600

A

600

A

Unit Body

SA

(Supply

Air)

Maintenance Space

RA

(Room

Air)

EA (Exhaust Air)

Heat Exchange Element

OA (Outside Air)

Inspection Opening

450

(For the inspection of Filters, Heat
Exchange Elements, Fans, Motors
and Damper.)

Maintenance Space

Unit Body

SA

(Supply

Air)

RA

(Room

Air)

EA (Exhaust Air)

Heat Exchange Element

OA (Outside Air)

(For the inspection of Filters, Heat
Exchange Elements, Fans, Motors
and Damper.)

Maintenance Space

Inspection Opening

450

Note) Model VN-250SE has one Heat Exchange Element.

Unit: mm

Model No.

A

VN-250SE

599

VN-350SE

804

VN-500SE

904

Note) Model VN-1KSAE has four Heat Exchange Elements.

Unit: mm

Model No.

A

VN-800SE

884

VN-1KSAE

1134

20

A

(1) Excessive bending

(2) Multi-times bending

(3) Making the connecting duct smaller

A

B

C

C'

B'

Dry-bulb temperature (° C)

A

b

so

lu

te

hum

idity

(kg

/kg

’)

S

at

ua

tio

n

C

ur

ve

FY250_CON-EN.fm Page 2 Friday, June 7, 2002 7:19 PM

Summary of Contents for VN-1KSAE

Page 1: ...IS DEUTSCH ITALIANO ESPAÑOL NEDERLANDS PORTUGUÊS ΕΛΛΗΝΙΚΗ Heat Exchange Ventilators Installation Manual Model No VN 250SE VN 350SE VN 500SE VN 800SE VN 1KSAE VN 500SE FY250_CON CV fm Page 1 Friday June 7 2002 8 52 PM ...

Page 2: ...rough direct connection to the power terminals Depending upon the environment for installation it becomes necessary to install an earth leakage breaker Install the power line and the connecting line with accuracy so the power source cover may not float If the installation of the power source cover is inappropriate the pin connection area is likely to cause a heat generation a fire and an electric ...

Page 3: ... the unit and goes out of the saturation curve as shown by Point C In this case the unit will be dewed or frosted To avoid this you are required to heat a low temp air B up to B so as to get C below the saturation curve before using the unit Never fail to make the inspection opening at the specific place on the ceiling so you can perform the constant cleaning or the equipment checking of filter an...

Page 4: ...itions Indoor air here means air in air conditioned living rooms Its use in refrigerators or other places where temperature can fluctuate greatly is prohibited even if a temperature range is acceptable Example Indoor air conditions During cooling period Temperature 27 C relative humidity 50 During heating period Temperature 20 C eelative humidity 40 Pipe Hood Outside Intake Duct Supply Air Duct Ce...

Page 5: ... 250SE has one Heat Exchange Element Number Name Quantity Note 1 Frame 1 2 Adapter 4 3 Terminal 1 4 Inspection Cover 1 5 Fan 2 6 Motor 2 7 Heat Exchange element 2 Note 8 Filter 2 9 Damper 1 10 Damper Motor 1 11 Ceiling Suspension Fixture 4 12 Electrical Equipment Box 1 EA Exhaust Air OA Outside Air RA Room Air SA Supply Air 4 13x30 Oval Hole 8 5 2 6 10 11 1 7 9 A H I H E F G G K L M 4 M 2 N P C C ...

Page 6: ...tor perform wiring in accordance with the laws and regulations of the country concerned Connect the broken lines in the wiring diagram We recommend that you use a switch having more than 3 mm distance to break contact and more than 15A rated current Ceiling Suspension Bolt φ10 to φ12 Fig 1 Nut Washer Ceiling Suspension Fixture Washer Nut 1 2 3 4 5 6 7 1 2 3 4 5 1 2 3 4 5 1 2 3 5 6 7 8 1 3 5 7 8 1 ...

Page 7: ...on of wiring check again there are no wrong wirings before power ON 1 2 3 4 5 6 7 1 2 3 4 5 1 MS 2 3 4 5 1 2 3 5 6 7 8 1 3 5 7 8 1 3 5 7 CN SAFM CN EAFM CN DM 3 1 4 1 NC NO CM RY3 RY5 RY2 RY1 RY4 CN8 CN6 CN5 CN7 NO NC CM NO NC CM NO CM NO NC CM RY4 RY3 RY5 RY2 RY1 TM1 4 3 2 1 6 7 5 COMMON L N LOW HIGH DAMPER 4 3 2 1 6 7 5 TM1 COMMON L N LOW HIGH DAMPER 1 2 3 4 5 6 Supply Air Fan Red Orange Exhaust...

Page 8: ...l to check wirings and perform a pilot running After completion of wiring power ON and perform a pilot run according to the following steps for checking a airflow condition and a damper operation Check the opening and closing of a damper by opening the inspection cover of the side of the unit Model No VN 800SE VN 1KSAE two Fan Motors are stopped during an operation of the damper In case that any a...

Page 9: ... under our sole responsibility that the product Heat Exchange Ventilator to which this declaration relates is in conformity with the provisions of Council Directive 89 336 EEC Electromagnetic Compatibility and 73 23 EEC Low Voltage Directive TJ0291 Printed in Japan FY250_CON CV fm Page 2 Friday June 7 2002 8 52 PM ...

Reviews: