2.4 LED Display
2
2.4 LED Display
The LEDs on the EN311 front panel indicate the status of the system. These LEDs show
the operating state of the EN311.
The combinations of the RUN LED and the STBY LED indicate the module state (run,
standby or down).
* See section 4.8, "Operating Mode Control Requests", for detailed information on run,
standby and down modes.
Table 2-1 LED Descriptions
LED
Description
RUN (Run)
Green
Indicates whether or not the module is operating normally.
On . . . . . The module is operating normally.
Off . . . . . A module error occurred.
STBY (Standby)
Red
Indicates the operating mode while the module is operating normally or the
outline of the cause when the module is down.
On . . . . . Standby (while operating normally)
Off . . . . . Run (while operating normally)/self-diagnostic error (when the
module is down)
Blinking . The module went down while operating (when the module is
down).
SEND (Send)
Green
Indicates whether or not the module is transmitting data.
On . . . . . Data transmission in progress
Off . . . . . No data is being transmitted.
RCV (Receive)
Green
Indicates whether or not the module is receiving data from the transmission
line.
On . . . . . Data is present on the transmission line.
Off . . . . . The transmission line is empty.
COL (Collision)
red
Indicates whether or not a collision is occurring on the transmission line
during a data transmission.
On . . . . . Collision(s) occurred.
Off . . . . . No collisions occurred.
ACC (Access)
Green
Indicates whether or not the S controller is accessing the module.
On . . . . . The S controller is accessing the module.
Off . . . . . The S controller is not accessing the module.
EXT. POWER
(External Power)
Green
Indicates whether or not 12-V DC power is supplied to the MAU power
supply terminal block.
On . . . . . The 12-V power is supplied normally.
Off . . . . . The 12-V power is either not supplied.
Note that this LED will not light unless the S controller power is turned on.
Combination of LEDs
Description
RUN on, STBY on
The module is operating normally in standby mode
(Parameter setting wait state)*
RUN on, STBY off
The module is operating normally in run mode
(Data transfer ready state)*
RUN off, STBY blinking
An error occurred while the module was operating (Down mode)*
RUN off, STBY off
An error was detected during power-on self-diagnostics
(Down mode)*
Summary of Contents for V Series
Page 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Page 12: ......
Page 16: ......
Page 34: ......
Page 40: ......
Page 106: ......
Page 180: ......
Page 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Page 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Page 224: ......
Page 240: ......
Page 244: ......
Page 248: ......
Page 250: ......
Page 256: ......
Page 258: ......