Ethernet module User’s Manual
Chapter 9 Installation and Wiring
9
<<Microcomputer Application Measurement/Control Installation Environment
Guideline>>
(Source: Japan Electric Measuring Instruments Manufacturers' Association)
When using cable ducts, install steel separators to separate power cables from
coaxial cables as shown in the figure below.
Figure 9-1 Duct Internal Layout Example
When laying cables in a pit, use separators in the same manner as when ducts are
used.
Figure 9-2 Pit Internal Layout Example
Table 9-3 Recommended Minimum Separation Distance
(Covered metal ducts and metal pipe) (Units: mm)
Cable installation method
Covered metal ducts or metal pipe
Parallel separation
Up to 10
meters
Up to 25
meters
Up to 100
meters
Up to 200
meters
Up to 500
meters
501
meters or
over
Power c
a
b
le
Up to 125 V, up to 10 A
10
10
50
100
200
250
Up to 250 V, up to 50 A
10
50
150
200
250
250
Up to 400 V, up to 100 A 50
100
200
250
250
250
Up to 500 V, up to 200 A 100
200
250
250
250
250
Levels exceeding the
above
At least 500
Power cable
Instrumentation power line
Solenoid and other control signals
Transmission cable
Separator
Metal duct
Power source
Ground (with a resistance to
ground of 100
Ω
or less)
Signal lines
Separator (steel)
Summary of Contents for V Series
Page 1: ...6F8C0904 Integrated Controller V Series Ethernet module EN311 User s Manual Sep 30 2004 ...
Page 12: ......
Page 16: ......
Page 34: ......
Page 40: ......
Page 106: ......
Page 180: ......
Page 199: ...6F8C0904 179 7 5 RAS Information Readout 7 Figure 7 1 Packet Format IP Datagram ...
Page 200: ...180 Ethernet module User s Manual Chapter 7 RAS Information 7 ...
Page 224: ......
Page 240: ......
Page 244: ......
Page 248: ......
Page 250: ......
Page 256: ......
Page 258: ......