E6582062
2-27
2. Installation and wiring
2
3
9
10
2. 3. 2
Standard connection method
The wiring of the power supply and motor is connected to the power terminal block and the wiring of
external control equipment such as control signals to the control terminal block.
■
Connection to power supply and motor
This diagram shows a standard wiring of the power circuit.
Connection to the power supply and motor wiring is common to all the types.
■
Connection to peripheral devices
This diagram shows an example of connection to peripheral devices.
WARNING
Prohibited
• Do not connect power supply to the output (motor side) terminals [U/T1], [V/T2] and [W/T3].
Connecting power supply to the output will damage the inverter and result in fire.
• Do not insert a braking resistor between DC terminals [PA/+] and [PC/-] or [PO] and[PC/-].
• Do not touch wires of equipment (e.g. ELCB) that is connected to the inverter power side at
Be
grounded
• The grounding wire must be connected securely.
R/L1
Connect the power supply
to [R/L1], [S/L2], and [T/L3].
Connect the motor to [U/T1],
[V/T2], and [W/T3].
VF-AS3
Molded-case
circuit breaker
or
Earth leakage
circuit breaker
Power supply
E
Motor
S/L2 T/L3
U/T1 V/T2 W/T3
VF-AS3
V/T2
U/T1
W/T3
S/L2
R/L1
T/L3
PB
PA
Molded-case
circuit breaker
Note 2)
Magnetic
contactor
Input
reactor
Power
supply
Motor
M
Motor-end surge voltage
suppression filter
Zero-phase
reactor
Note 1) Connect between PA/+ and PC/-
when mounting to a braking unit.
Note 2) Or Earth leakage circuit breaker.
Braking resistor
Note 1)
PO
PA/+
DC reactor
(frame size A7 and A8
attached in the package)
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...