6. [Advanced] How to use parameters
3
4
6
9
6. 24. 3 Detecting the stall time during power running to trip
<F452: Stall detection time during power running>
<F441: Power running torque limit level 1>
<F601: Stall prevention level 1>
■
Function
This function is one of the functions to prevent lifting gear from falling. If stall prevention operation
occurs in succession, this function judges that the motor has stalled to trip it.
■
Parameter setting
■
Setting method
1) In case of overcurrent stall
If, during power running, the output current reaches the value for <F601: Stall prevention level
1> or more, and continues for the period of time set for <F452: Stall detection time during
power running>, the trip "Ot2" will occur.
Title
Parameter name
Adjustment range
Unit
Default setting
F452
Stall detection time
during power running
0.00-10.00
s
0.00
F441
Power running torque
limit level 1
0.0-249.9
250.0: Disabled
%
250.0
F601
Stall prevention level 1
10-200 (HD)
10-160 (ND)
%
150(HD)
120(ND)
0.0Hz
STOP
13:45
F452 : Power stall detection time
Min: 0.00
Max: 10.00
X1000
X100
X10
X1
0.00
s
“0t2” Trip
Output frequency (Hz)
Output current (%)
Below
<F452>
Time (s)
Time (s)
<F601>
<F452>
Summary of Contents for TOSVERT VF-AS3
Page 2: ...1 9 ...
Page 14: ......
Page 17: ...E6582062 iii I 3 9 15 Warranty 15 1 16 Disposal 16 1 ...
Page 18: ......
Page 34: ......
Page 438: ......
Page 458: ......
Page 470: ......
Page 482: ......
Page 502: ......
Page 572: ......
Page 590: ......
Page 608: ......
Page 616: ......
Page 618: ......
Page 620: ......
Page 621: ...1 3 9 10 ...