background image

Central remote controller

Owner’s Manual

23

-EN

You can change the set temperature, operation mode, fan speed, and louver.
Depending on the range of the area to be set, display and operate the “Control” screen of All, Zone, or Unit.

Changing air conditioner Settings (Set Temperature, Operation Mode, Fan 

Speed, and Louver)

1

Display the “Control” screen of All, Zone, or Unit (P.15)

2

Use [<] and [>] to select the item to change.

For details of the setting of each item, see the table below.

3

Make changes using [

] and [

], and then press [

] (Confirm).

• The changes to the settings are not reflected on the air conditioner 

unless you press [ ] (Confirm).

1

2

3

4

No.

Item

Description

1

Set temperature

You can change the set temperature using [

] and [

].

 

NOTE

• The set temperature cannot be changed when the operation mode is Fan.
• The temperature range that can be set differs depending on the operation mode.
• If a temperature outside the set temperature range of the relevant operation mode is set, the 

temperature is changed to the upper- or lower-limit temperature of the range.

2

Operation mode

You can change the operation mode using [

] and [

].

 

NOTE

The operation modes that cannot be set are not displayed.

3

Fan speed

You can change the fan speed using [

] and [

].

 

NOTE

• The fan speeds that cannot be set are not displayed.
• A blank is displayed if the fan speed is fixed.

4

Louver

You can change the louver to the following, using [

] and [

].

 

NOTE

• The louver position may differ for the header and follower units.
• The setting range differs depending on the operation mode.

AUTO

HEAT

COOL

FAN

DRY

Swing

Swing stopped

F1

F2

F3

F4

F5

Operation Mode

Setting range

Auto (Cool), Cool, Dry

Swing 

 Swing stopped 

 F1 

 F2 

 F3 

 Swing (back to 

the beginning)

Auto (Heat), Heat, Fan

Swing 

 Swing stopped 

 F1 

 F2 

 F3 

 F4 

 F5 

 

Swing (back to the beginning)

Summary of Contents for TCB-SC640U-E

Page 1: ...a del Manual de instalación y del Manual del propietario Eesti Paigaldusjuhendi ja kasutusjuhendi allalaadimine Suomi Asennusohjeiden ja käyttöohjeiden lataaminen Français Téléchargement du manuel d installation et du manuel du propriétaire Hrvatski Preuzimanje Instalacijskog priručnika i Vlasničkog priručnika Magyar Telepítési kézikönyv és Felhasználói kézikönyv letöltése Italiano Download del Ma...

Page 2: ...ion of All air conditioners 20 Start Stop Operation of All air conditioners in a Zone 21 Start Stop Operation of an Individual air conditioner 22 Changing air conditioner Settings Set Temperature Operation Mode Fan Speed and Louver 23 Setting the Operating Schedule 24 Changing the Operating Schedule Operating Sch Enable Void and Operating Sch settings 26 Changing the details of the Operating Sched...

Page 3: ...tilation mode and fan speed Ventilation 49 Limit the output of the air conditioner Energy saving operation 51 Lock the local remote control operation Key lock 52 Make all the louver settings in the group at once Louver setting in Group 53 5 2 Air to Water Heat Pump 54 Setting the Operation Details 54 Auto mode 55 Frost protection 55 Anti bacteria 56 Night setback 56 Unit Information 57 6 Administr...

Page 4: ...r Sign Reset P 48 To operate the Air to air heat exchanger Set the ventilation function ventilation mode and fan speed Ventilation P 49 To make energy saving settings Limit the output of the air conditioner Energy saving operation P 51 To restrict the local remote control operation Lock the local remote control operation Key lock P 52 Basic Usage To start stop the Air to Water Heat Pump operation ...

Page 5: ...e to property refers to extended damage related to houses household goods livestock or pets etc WARNING Request installation Ask the dealer from whom you purchased the unit or a professional for installation work Installation requires specialised technical expertise If you attempt to perform installation work yourself and perform the work incorrectly it may cause fire electric shock or injury Use ...

Page 6: ...install this product in a place where combustible gas may leak Gas leaking and accumulating around the product may cause a fire Check the installation location Do not use this device in locations where children may be present Prohibited Do not drop the product or apply strong shock Doing so may cause a failure If anything is abnormal turn off the power If this product malfunctions turn off the ori...

Page 7: ...vice A device whose set temperature and operation mode cannot be controlled or monitored The major devices include the light settings Air to air heat exchanger and ventilating fan System Configurations Zone 1 Central remote controller 10 Zones up to a total of 64 units All Set all air conditioners at once Unit Set the air conditioners individually Zone All air conditioners or ON OFF devices are di...

Page 8: ... are stopped 3 Check lamp Lights in red if an abnormality occurs Please contact the dealer from whom you purchased the unit 4 button Press to start operation 5 button Press to stop operation 6 Control button Press to display the Control screen or the Menu screen for controlling air conditioners 7 buttons Press to select setting item 8 Confirm button Press when switching screens from All to Zone to...

Page 9: ... Control screen of Unit 7 Displayed when Energy saving operation is set P 51 8 Displayed when this unit is set to Local Control Mode 9 Displayed when the operation of the local remote control connected to each air conditioner is restricted For details see Lock the local remote control operation Key lock P 52 10 Displayed when Bypass is set 11 Displayed when Automatic is set 12 Displayed when Heat ...

Page 10: ...ights when Night setback operation is set to ON and heating or cooling is selected 6 Lights while hot water boost is actually running 7 Lights when the compressor is acting 8 Lights while the electric heater inside the Hydro Unit is energized during a heating operation 9 Lights while the electric cylinder heater is energized during hot water operation 10 Lights while internal pump 1 is driven 11 L...

Page 11: ... restricted by Key lock is displayed 5 The number of air conditioners with filter cleaning indications is displayed If an abnormality occurs the display changes to the number of abnormal air conditioners If a notice occurs the display changes to the number of air conditioners for which the notice has occurred 6 The Button Operation Guide is displayed 7 The number of air conditioners in operation i...

Page 12: ...ty is as follows Check Notice Filter Displayed for an abnormal air conditioner Displayed for an air conditioner for which a notice has occurred Displayed when there is an air conditioner that requires filter cleaning No Functions 1 The operation status is displayed During operation is displayed when stopped is displayed 2 The currently displayed control range All Zone or Unit Address Line indoor c...

Page 13: ... function When you have changed any individual setting using the local remote control after changing the settings on the Control screen of All or Zone If you press Confirm with displayed the air conditioner is not set A blank is displayed if there is a function whose settings cannot be changed The screen shown at the left is an example of the model having a fixed louver Blank spaces cannot be sele...

Page 14: ...s 4 If disabled items will be displayed in gray 5 The set temperature is displayed 6 The operation mode is displayed 7 The order of display priority is as follows Check Lock Displayed for an abnormal Air to Water Heat Pump Displayed when Key lock is set No Functions 1 The operation status is displayed During operation is displayed when stopped is displayed 2 The currently displayed control range A...

Page 15: ...buttons as follows Changing Screens Air conditioner All screen Zone screen Unit screen All Control screen Zone Control screen Unit Control screen All Menu screen Zone Menu screen Unit Menu screen Return button Confirm button Control button Confirm Return Confirm Return Control Return Control Return Control Return Control Return Control Return Control Return ...

Page 16: ...tons as follows Changing Screens Air to Water Heat Pump All screen Zone screen Unit screen All Control screen Zone Control screen Unit Control screen All Menu screen Zone Menu screen Unit Menu screen Return button Confirm button Control button Confirm Return Confirm Return Control Return Control Return Control Return Control Return Control Return Control Return ...

Page 17: ...ght of the All Zone or Unit screen blinks The retention period in case of a power outage is approximately 3 days If power is not supplied for a long period of time the clock is initialized to 2020 01 01 00 00 Setting the Clock Clock 1 In the Settings Menu screen select Clock and then press Confirm The Clock setting screen is displayed 2 In the Clock setting screen select Clock and then press Confi...

Page 18: ... is displayed 2 Select ON or OFF using and and then press Confirm If ON is set and the time set in Start date is reached the clock is advanced by 1 hour When the time set in End date is reached the clock is restored to the original time If you press Return the Daylight saving screen is displayed again During the Daylight saving period is displayed above the clock 1 In the Daylight saving screen se...

Page 19: ... the First Day of the Week First Day 1 In the Settings Menu screen select Schedule settings and then press Confirm The Schedule settings screen is displayed 2 Select First day using and and then press Confirm The First day screen is displayed 3 Select a day of the week using and and then press Confirm The selected day of the week is set If you press Return the Schedule settings screen is displayed...

Page 20: ...ut all at once Start Stop Operation CAUTION Always turn off the power circuit breaker if the product malfunctions due to lightning or wireless etc during operation Cause of failure Start Stop Operation of All air conditioners 1 Display the All screen P 15 To start 2 Press The confirmation screen is displayed 3 Press to select Yes then press Confirm All air conditioners start operation and the Run ...

Page 21: ...een P 15 2 Press to select a Zone The selected Zone is highlighted To start 3 Press The confirmation screen is displayed 4 Press to select Yes then press Confirm All air conditioners in the selected Zone start operation and changes to To stop 3 Press The confirmation screen is displayed 4 Press to select Yes then press Confirm All air conditioners in the selected Zone stop operation and changes to...

Page 22: ...ouver P 23 Start Stop Operation of an Individual air conditioner 1 Display the Unit screen P 15 2 Press to select a Zone then press to select an air conditioner To start 3 Press The selected air conditioner starts operation and changes to To stop 3 Press The selected air conditioner stops operation and changes to 3 3 2 Start Stop ...

Page 23: ... Fan The temperature range that can be set differs depending on the operation mode If a temperature outside the set temperature range of the relevant operation mode is set the temperature is changed to the upper or lower limit temperature of the range 2 Operation mode You can change the operation mode using and NOTE The operation modes that cannot be set are not displayed 3 Fan speed You can chang...

Page 24: ...isplayed 3 Select Operating Sch settings using and and then press Confirm The Select Zone screen is displayed 4 Select the zone to set using and and then press Confirm The Weekly display screen of the selected zone is displayed 5 Press Control The Weekly Schedule screen is displayed In the Weekly display screen you can make the Operating Schedule void or set the unit to operate according to the sp...

Page 25: ...time using and You cannot switch the operation unless you set the time 8 Place the cursor on Operation switching using and switch to ON or OFF using and and then press Confirm The Weekly Schedule screen is displayed again with the set schedule added to the list If you press Return without pressing Confirm the setting is cancelled and the screen returns to the state it was in before the change was ...

Page 26: ...nged you can set the temperature in that range Operating Sch Enable Void Changing the Operating Schedule Operating Sch Enable Void and Operating Sch settings Changing the details of the Operating Schedule settings 1 In the Settings Menu screen select Schedule settings and then press Confirm The Schedule settings screen is displayed 2 Select Operating Sch Enable Void using and and then press Confir...

Page 27: ...ange Enable Void and Special day using and and then press Confirm The cursor moves to the week of the Weekly display If you press Return without pressing Confirm the setting is cancelled and the screen returns to the state it was in before the change was made If you do not press Confirm after making the change you cannot switch to the Weekly Schedule screen You can make the settings for up to 5 we...

Page 28: ...E If the time is not set you cannot set ON OFF set temperature operation mode or key lock 2 ON OFF You can change ON OFF using and NOTE If you set the last state is maintained 3 Set temperature You can change the set temperature using and NOTE If you set the last set temperature is maintained to continue the operation 4 Operation mode You can change the operation mode to the following using and NO...

Page 29: ... is registered you cannot perform the copy operation Only the zones for which an air conditioner is registered are displayed The copy source zone is not displayed Multiple copy destinations can be selected You cannot copy the schedule set in an ESTIA zone to an air conditioner zone 4 After selecting the copy destination press Control Copy Complete is displayed and the Select Zone screen is display...

Page 30: ...Operating Sch settings P 27 2 Place the cursor on the schedule you want to delete in the Weekly Schedule screen and the press Control The Delete schedule confirmation screen is displayed You cannot delete a schedule if no schedule is set 3 Select Yes using and and then press Confirm The selected schedule is deleted and the Weekly Schedule screen is displayed again If you select No and the Weekly S...

Page 31: ... or the day set as a special day and the press Control The Weekly Schedule screen is displayed Weekly Schedule 3 Select Sp1 or Sp2 using and and the schedule to set using and and then press Confirm The Schedule editing screen is displayed No more than 8 schedules can be set a day Sp1 Special day 1 Sp2 Special day 2 Schedule editing 4 Move the cursor using and and set the time using and If the time...

Page 32: ...creen is displayed The zones for which no air conditioner is registered are not displayed 3 Select the zone to set using and and then press Confirm The Weekly Schedule screen is displayed You cannot set an Energy saving Schedule for a zone where Air to Water Heat Pump is set 4 Select the day of week to set using and and the schedule to set using and and then press Confirm The Schedule editing scre...

Page 33: ... is cancelled If there is only one zone for which an air conditioner is registered you cannot perform the copy operation Only the zones for which an air conditioner is registered are displayed The copy source zone is not displayed Multiple copy destinations can be selected 4 After selecting the copy destination press Control Copy Complete is displayed and the Select Zone screen is displayed again ...

Page 34: ...ails of the Energy Saving Schedule settings P 32 2 Place the cursor on the schedule you want to delete in the Weekly Schedule screen and the press Control The Delete schedule confirmation screen is displayed You cannot delete a schedule if no schedule is set 3 Select Yes using and and then press Confirm The selected schedule is deleted and the Weekly Schedule screen is displayed again If you selec...

Page 35: ... breaker if the product malfunctions due to lightning or wireless etc during operation Cause of failure Start Stop Operation of All Air to Water Heat Pumps 1 Display the All screen P 16 To start 2 Press The confirmation screen is displayed 3 Press to select Yes then press Confirm All Air to Water Heat Pump start operation and the Run lamp lights up To stop 2 Press The confirmation screen is displa...

Page 36: ... to select a Zone The selected Zone is highlighted To start 3 Press The confirmation screen is displayed 4 Press to select Yes then press Confirm All Air to Water Heat Pump in the selected Zone start operation and changes to To stop 3 Press The confirmation screen is displayed 4 Press to select Yes then press Confirm All Air to Water Heat Pump in the selected Zone stop operation and changes to 3 3...

Page 37: ...tion of an Individual Air to Water Heat Pump 1 Display the Unit screen P 16 2 Press to select a Zone then press to select an Air to Water Heat Pump To start 3 Press The selected Air to Water Heat Pump starts operation and changes to To stop 3 Press The selected Air to Water Heat Pump stops operation and changes to 3 3 2 Start Stop ...

Page 38: ... using and and then press Confirm The changes to the settings are not reflected on the Air to Water Heat Pump unless you press Confirm 1 2 3 4 No Item Description 1 ZONE1 Z1 You can change the set temperature using and NOTE If there is no ZONE1 this will be blank 2 ZONE2 Z2 You can change the set temperature using and NOTE If there is no ZONE2 this will be blank 3 Operation mode You can change the...

Page 39: ...isplayed 3 Select Operating Sch settings using and and then press Confirm The Select Zone screen is displayed 4 Select the zone to set using and and then press Confirm The Weekly display screen of the selected zone is displayed 5 Press Control The Weekly Schedule screen is displayed In the Weekly display screen you can make the Operating Schedule void or set the unit to operate according to the sp...

Page 40: ...time using and You cannot switch the operation unless you set the time 8 Place the cursor on Operation switching using and switch to ON or OFF using and and then press Confirm The Weekly Schedule screen is displayed again with the set schedule added to the list If you press Return without pressing Confirm the setting is cancelled and the screen returns to the state it was in before the change was ...

Page 41: ... Changing the Operating Schedule Operating Sch Enable Void and Operating Sch settings Changing the details of the Operating Schedule settings 1 In the Settings Menu screen select Schedule settings and then press Confirm The Schedule settings screen is displayed 2 Select Operating Sch Enable Void using and and then press Confirm The Select Zone screen is displayed 3 Select the zone to change using ...

Page 42: ...ange Enable Void and Special day using and and then press Confirm The cursor moves to the week of the Weekly display If you press Return without pressing Confirm the setting is cancelled and the screen returns to the state it was in before the change was made If you do not press Confirm after making the change you cannot switch to the Weekly Schedule screen You can make the settings for up to 5 we...

Page 43: ...Time Change the time using and NOTE If the time is not set you cannot set ON OFF set temperature operation mode or key lock 3 ON OFF You can change ON OFF using and NOTE If you set the last state is maintained 4 Set temperature You can change the set temperature using and NOTE If you set the last set temperature is maintained to continue the operation 5 Operation mode You can change the operation ...

Page 44: ... is registered you cannot perform the copy operation Only the zones for which an air conditioner is registered are displayed The copy source zone is not displayed Multiple copy destinations can be selected You cannot copy the schedule set in an air conditioner zone to an ESTIA zone 4 After selecting the copy destination press Control Copy Complete is displayed and the Select Zone screen is display...

Page 45: ...Operating Sch settings P 42 2 Place the cursor on the schedule you want to delete in the Weekly Schedule screen and the press Control The Delete schedule confirmation screen is displayed You cannot delete a schedule if no schedule is set 3 Select Yes using and and then press Confirm The selected schedule is deleted and the Weekly Schedule screen is displayed again If you select No and the Weekly S...

Page 46: ... or the day set as a special day and the press Control The Weekly Schedule screen is displayed Weekly Schedule 3 Select Sp1 or Sp2 using and and the schedule to set using and and then press Confirm The Schedule editing screen is displayed No more than 8 schedules can be set a day Sp1 Special day 1 Sp2 Special day 2 Schedule editing 4 Move the cursor using and and set the time using and If the time...

Page 47: ...tems see below The displayed items differ depending on the control range Setting items Description Page to see Filter Sign Reset Used to cancel the Filter Sign P 48 Ventilation Used to control the Air to air heat exchanger ventilation only indoor unit linked with the air conditioner This menu item is available when only the Air to air heat exchanger is used P 49 Energy saving operation Used for en...

Page 48: ...ng time to clean the filter is reset REQUIREMENT After cleaning the filter be sure to perform Filter Sign Reset Operation after filter cleaning Filter Sign Reset 1 Display the Control screen of All Zone or Unit P 15 2 Press Control The Menu screen is displayed 3 Use to select Filter Sign Reset then press Confirm The Admin Password Entry screen is displayed 4 Enter the 4 digit password then press C...

Page 49: ...ion ventilation mode and fan speed Ventilation 1 Display the Control screen of All Zone or Unit P 15 2 Press Control The Menu screen is displayed 3 Press to select Ventilation then press Confirm The Ventilation screen is displayed 4 Press to select ON OFF then press Confirm The ON OFF screen is displayed 5 Press to select ON or OFF then press Confirm Start or stop operation then press Return to re...

Page 50: ... air and return air and making the temperature and humidity of the outdoor air closer to those of the return air before supplying it Bypass Outdoor air is taken into a room as it is 1 Perform steps 1 to 3 of Ventilation ON OFF P 49 2 Press to select Fan speed then press Confirm The Fan speed screen is displayed 3 Press to select the fan speed then press Confirm The selected fan speed is set Press ...

Page 51: ...ing operation 1 Display the Control screen of All or Zone P 15 2 Press Control The Menu screen is displayed 3 Press to select Energy saving operation then press Confirm The Energy saving operation screen is displayed 4 Select the save rate using and and then press Confirm The selected save rate is set If you press Return the Menu screen is displayed again 2 3 4 All Control screen Setting items Des...

Page 52: ...ber of air conditioners for which Key lock is set for Lock on the All screen is displayed Lock the local remote control operation Key lock 1 Display the Control screen of All Zone or Unit P 15 2 Press Control The Menu screen is displayed 3 Press to select Key lock then press Confirm The Key lock screen is displayed 4 Press to select the item you wish to set then press Confirm The selected item is ...

Page 53: ...Display the Control screen of All Zone or Unit P 15 2 Press Control The Menu screen is displayed 3 Select Louver setting in Group using and and then press Confirm The Admin Password Entry screen is displayed 4 Enter a 4 digit password and then press Confirm Select the digit position using and and select a number using and The Louver setting in Group screen is displayed 5 Select ON or OFF using and...

Page 54: ...splayed items differ depending on the control range Setting items Description Page to see Auto mode The setting temperature can be set automatically according to the outside temperature P 55 Frost protection This function performs operation with the minimum capacity target water temperature 15 C to prevent pipes from freezing in case the unit is not used for a long period due to absence P 55 Anti ...

Page 55: ...rm The Auto mode screen is displayed 4 Select ON or OFF using and and then press Confirm If you press Return the Menu screen is displayed again Frost protection 1 Display the Control screen of All Zone or Unit P 16 2 Press Control The Menu screen is displayed 3 Select Frost protection using and and then press Confirm The Frost protection screen is displayed 4 Select ON or OFF using and and then pr...

Page 56: ...reen is displayed 4 Select ON or OFF using and and then press Confirm If you press Return the Menu screen is displayed again Night setback 1 Display the Control screen of All Zone or Unit P 16 2 Press Control The Menu screen is displayed 3 Select Night setback using and and then press Confirm The Night setback screen is displayed 4 Select ON or OFF using and and then press Confirm If you press Ret...

Page 57: ...ormation 1 Display the Control screen of Unit P 16 2 Press Control The Menu screen is displayed 3 Select Unit Information using and and then press Confirm The Unit Information screen is displayed 4 Select ON or OFF using and and then press Confirm If you press Return the Menu screen is displayed again ...

Page 58: ...played Delete the default name displayed at the top of the screen before entering characters 4 Select characters using and and then press Confirm The selected characters are displayed at the top of the screen Up to 9 characters can be entered 5 Repeat step 4 select Fix and then press Confirm The zone name is changed to the one you have set and the Zone Name Settings screen is displayed again If yo...

Page 59: ...lect the language using and and then press Confirm The selected language is set If you press Return the Screen Display Settings screen is displayed again 1 Select Screen Contrast using and and then press Confirm The Screen Contrast screen is displayed 2 Move using and and then press Confirm The adjusted contrast is set If you press Return the Screen Display Settings screen is displayed again 1 Sel...

Page 60: ...or OFF do not sound using and and then press Confirm The selected item is set If you press Return the Button Settings screen is displayed again 1 Select Button Long Press Settings using and and then press Confirm The Button Long Press Settings screen is displayed The current setting is displayed in 2 Select ON butt long press using and and then press Confirm The ON butt long press screen is displa...

Page 61: ... number of seconds 1 to 5 seconds using and and then press Confirm The selected number of seconds is set as the ON long press time If you press Return the ON butt long press screen is displayed again 1 In the Settings Menu screen select Button Settings and then press Confirm The Button Settings screen is displayed 2 Select Sensitivity Adjustment using and and then press Confirm The Sensitivity Adj...

Page 62: ...0 Check codes is displayed Change the page using and If you press Return the Check Notice history screen is displayed again The Check code for the occurring check is blinking 3 4 digit code Air conditioner LC VRF Air to air heat exchanger General purpose equipment control interface 3 Air to Water Heat Pump The Notice history of the past 300 Notice codes is displayed Change the page using and If yo...

Page 63: ...d 3 Enter a new password using and and then press Confirm The new password is set and the Settings Menu screen is displayed again The default administrator password is set to 0000 Checking the device information Information In the Settings Menu screen select Information and then press Confirm The model and software version are displayed If you press Return the Settings Menu screen is displayed aga...

Page 64: ...ote controller Even if you can configure the settings on the Control screen of All or Zone the controller does not operate when the air conditioner does not have the corresponding function The schedule is set but the device does not operate Is the clock not blinking not set Set the clock The clock is initialized if power is not supplied for a long period of time A button is pressed but there is no...

Page 65: ...n speed Energy saving operation Filter Sign Reset Monitor ON OFF Operation Mode Set temperature Fan speed Louver Key lock Ventilation ON OFF Ventilation mode Ventilation Fan speed Energy saving operation Filter Sign Check code Notice code Main functions Operating Schedule Setting target Zone Setting unit Day of week Setting range 6 weeks Special day 2 options Setting time 00 00 to 23 59 Setting co...

Page 66: ... Check code Main functions Operating Schedule Setting target Zone Setting unit Day of week Setting range 6 weeks Special day 2 options Setting time 00 00 to 23 59 Setting content ON OFF Set temperature Operation mode Key lock Maximum number of schedules per day 8 External input Number of points 3 Functions ON OFF Emergency system Night Operation Locking External output Number of points 2 Functions...

Page 67: ... fill this in at the time of purchase in case you need to request repair etc Model Name TCB SC640U E TCB SC640U TR TCB SC640U ME Installation Date Year Month Day Name of dealer from whom you purchased the unit Phone number DEB5219051 1 ...

Reviews: