Modbus INTERFACE

Installation Manual

Modbus Interface

Model name:

TCB-IFMB641TLE

Summary of Contents for TCB-IFMB641TLE

Page 1: ...Modbus INTERFACE Installation Manual Modbus Interface Model name TCB IFMB641TLE ...

Page 2: ...4 4 Installation 4 5 Connection of power cables earth wires communication cables 5 6 Setting 8 7 Test run check 9 8 TCB IFMB640TLE product replacement 10 Thank you very much for purchasing this TOSHIBA Modbus Interface Please read this manual carefully beforehand for proper installation of the Modbus Interface 1 EN ...

Page 3: ...tion or long term treatment as an outpatient 3 Damage to property indicates damage extending to buildings household effects domestic livestock and pets Symbols Meaning of Symbols Indicates prohibited items The actual contents of the prohibition are indicated by a picture or text placed inside or next to the graphic symbol Indicates compulsory mandatory items The actual contents of the obligation i...

Page 4: ...ls between TCC LINK and Modbus Master Specifications Note Modbus is a registered trade mark of Schneider Electric SA External view Power supply 220 240 VAC 50 60 Hz Power consumption 3 W Operating temperature humidity 0 to 40 C 10 to 90 RH no condensation Storage temperature 20 to 60 C Chassis material Galvanized sheet metal 0 8 t no coating Dimensions 66 H x 170 W x 200 D mm Mass 1 1 kg 146 9 170...

Page 5: ...lace exposed to rain outdoors under eaves etc Installation space and maintenance space A side space for connecting through cable inlets and an upper space for maintenance must be reserved before installation The other sides can be adjacent to surrounding objects No Item Quantity Remarks 1 Modbus Interface 1 2 Installation Manual 1 3 Screw 4 M4 x 12 mm tapping screws 4 Cable clamp 1 5 Clamp filter ...

Page 6: ...se as possible to the Modbus Interface unit 50 10 10 35 10 L N 55 10 50 10 Length of stripped RS 485 Shielded wire ends and TCC LINK communication cable Length of stripped RS 485 communication cable not shielded wire ends Length of stripped power cable Do not connect the shield wire to the earth It should be open and insulated Clamping communication cable Clamping RS 485 communication cable addres...

Page 7: ...ctors on interfaces with address of other than 1 The shielded wire ends must be insulated and left open Do not connect the shield wire to the terminal block It should be open and insulated The shielded wire of the TCC LINK communication cable must be earthed on the air conditioner TCC LINK U1 U2 FG RS 485 L N SW1 SW4 LED1 LED2 LED3 LED4 LED5 SW2 SW7 SW6 SW5 SW3 1 2 3 4 SG A B Air conditioner Modbu...

Page 8: ...remote controller TCC LINK U1 and U2 have no polarity Set the RS 485 terminator resistor on the address1 unit Modbus Interface address SW1 1 and host system Do not set it here TCC LINK terminator resistor is set on the air conditioner side SW6 should be OFF The shielded wire of the RS 485 communication cable must be earthed on address 1 CAUTION RS 485 communication cables A and B have polarity Be ...

Page 9: ...witch Set 120 ohm only when the Modbus interface address SW 1 and set open for other Modbus interfaces SW6 TCC LINK terminator resistor select switch The TCC LINK terminator resistor is set on the air conditioner side Set SW6 to open SW7 Reset switch When performing an address setting with SW1 push this reset switch after the address setting to read the set value U1 U2 FG A B SG L N TCC LINK RS 48...

Page 10: ...by LED5 Indoor unit or TCB IFCG1TLE central control address and SW1 SW2 setting Communication status with indoor unit LED5 Remarks Normal Lighting Error Blinking Communication with the indoor unit was established previously but is disabled currently Invalid indoor unit Light off Communication with the indoor unit has never been established Example Check the communication status of indoor unit with...

Page 11: ...nd the address switches of the TCB IFMB641TLE according to 6 Setting the same as the installed TCB IFMB640TLE For address 1 set the terminator of the RS 485 Switching variable specification To switch from the TCB IFMB641TLE variable specification to the TCB IFMB640TLE variable specification set bit1 of SW3 to ON When the power is turned on in this configuration operation will be the same as the TC...

Page 12: ...DEA0509101 ...