Connection Method

<Gas joint> 

Determine the installation orientation of the L-pipe according to the piping connections from the outdoor unit, and select a socket that matches 
the diameter of the locally procured pipes. 

<Liquid joint> 

Select a socket to match the diameter of the locally procured piping and install it. 

<Balance pipe joint> 

For 2 outdoor units system, connect directly between the header unit and the follower unit. 

3

Example of pipe connections 

Install and connect the piping between the outdoor units as shown in the diagram below. 

NOTE

There are no specific requirements on the length of the straight pipe before the joint for either the gas or liquid sides. 

<For connections to the front>

To outdoor unit 

Locally procured piping 

Locally procured piping 

To main pipe or to 

other joint 

Inlet 

Outlet (2) 

Outlet (1) 

Socket (Provided) 

Socket (Provided)

L-pipe (Provided)

Locally procured piping 

To outdoor unit or to 

other joint 

Gas joint (Provided)

Socket (Provided) 

Brazed locally

NOTE

• Select the socket (No.in 

) fitting to the pipe diameter 

connected to the outdoor unit.

• After cutting the pipe, be sure to remove the burrs and 

polish the end surface. When some squash or 
deformation, etc. occurs, improve the pipe insertion 
condition by using the flare tool.

• Confirm whether no dust, water, foreign matters, etc 

exists on the gas joint, the liquid joint, the balance pipe 
joint and the socket to be inserted.

Locally procured piping 

Socket (Provided) 

To main pipe or to 

liquid joint 

Socket (Provided) 

Liquid joint (Provided) 

To outdoor unit 

To outdoor unit or 

to other joint 

Locally procured piping 

Socket (Provided) 

Locally procured piping 

Balance pipe joint (provided) 

Locally procured piping 

To outdoor unit or 

to other joint 

To outdoor unit 

or to other joint 

Locally procured piping 

To outdoor unit 

Locally procured piping 

A

Outdoor unit 

connection piping kit 

L-pipe 

Balance pipe

Gas pipe

Locally procured 

piping 

Header unit A 

Liquid pipe

Follower unit B 

Follower unit C 

To indoor units

Balance

pipe joint

Liquid joint

Gas joint

A view

Horizontal line

Gas joint 

<For connections to the bottom>

Remove the knock-out hole from the bottom of the outdoor units. 
(Refer to the installation manual of the outdoor unit.) 

4

Heat insulating for pipes 

• Insulate the joints of the liquid pipe, gas pipe, and balance pipe individually. 
• Insulator for the liquid joint and the balance pipe joint are not provided. Please procure it locally. 

<Gas pipe> 

• Use heat insulators with heat resistance of 248 °F or more for the gas pipe. 
• In order to prevent dripping condensation, do not leave any gap between heat insulator for branching joint (included in package) and heat 

insulator for pipe (locally procured). And then, wrap the seam with heat insulator with thickness of 0.4" or more (locally procured).

How to apply the insulation to the gas joint 

<Liquid /balance pipe> 

• To heat insulate the T-joints, use a commercially available joint cover (for T-shape) that is with 0.4" or more thickness, or one applied with 

machining as shown in the figure. 

• Seal the T-joints completely without any gap to prevent condensation and dripping water. 

A

Locally procured 

piping 

Gas joint 

Balance

pipe

L-pipe

20"

 or mor

e

Header unit A 

Liquid pipe

Follower unit B 

Follower unit C 

To indoor units 

Gas pipe 

Liquid joint

Balance 

pipe 

joint 

A view

Horizontal line

Gas 

joint 

Heat insulator 

(Locally procured) 

Heat insulator

(Provided) 

Joint 

No gap

Taping (Locally procured) 

Taping (Locally procured) 

Heat insulator 

(Locally procured) 

Heat insulator

(Provided)

Locally procured 

piping heat insulator 

(with thickness of 0.4" 

or more)

No gap

Locally procured 

piping insulator 

(with thickness of 

0.4" or more)

6"

Seal with vinyl tape 

90°  cutout 

Insulated pipe

90°

Seal the seams with 

urethane foam 

Insulated pipe

Heat insulator

Diameter of 

insulated pipe joint 

Cut at 90°  

4" 

or 

mo

re

ØD

ØD