1. Preparation for attaching ceiling panel

 

„

Checking indoor unit position

1.  Check the position of the indoor unit using the Installation 

Manual.

2.  Check whether the ceiling opening size falls within a range 

of 860 × 860 to 910 × 910.

3.  Determine the positional relation between the ceiling and 

the indoor unit using the installation gauge supplied with 
the indoor unit. Improper positioning of the indoor unit may 
result in air/water leakage or malfunction of the louver.

• 

Do not put the ceiling panel facing down or lean 
it against a wall, etc. or put it on an object with 
projection to avoid scratches on the surface.

  Handle the ceiling panel carefully so as not to deform 

the movable hooks.

This clearance must be 12 to 17.
A clearance outside this range may cause malfunction.

Indoor unit

Ceiling opening size

Ceiling

Installation gauge
(supplied with the indoor unit)

12 to 17

2. Attaching ceiling panel to indoor unit

 

„

Detaching air intake grille

Air intake grille

Ceiling panel

Adjust corner cap

Knobs of air intake grille hooks

2

Safety strap 
hook

Ceiling panel hook hole

Hinges

1

Knob

Adjust 
corner 
cap

Adjust corner 
cap

Strap

Ceiling panel

Open

Keep the bracket 
open.

Closed

Panel 

fi

 xing 

bracket

Open

Close

(Fig. 1)

(Fig. 2)

1.  Slide the knobs of the hooks of the air intake grille in the 

direction of arrow 

1

, and open the grille.

2.  Release the safety strap hook from the ceiling panel.

• 

Do not remove the safety strap screw on the air 
intake grille side.

3.  Remove the hinges on the air intake grille from the ceiling 

panel in the direction of arrow 

2

 with the grille open.

 

„

Detaching adjust corner caps

1.  Pull the knob of the adjust corner cap in the direction of 

arrow 

1

, and detach the adjust corner caps from the four 

corners.
•  The knob is provided only on one side of the cap. 

Detach the adjust corner caps from the knob side.

 

„

Checking panel 

fi

 xing bracket position

After the adjust corner caps are detached, check that the 
panel 

fi

 xing bracket is open (Fig. 1).

•  The ceiling panel cannot be attached to the indoor unit with 

the bracket closed (Fig. 2).

Summary of Contents for RBC-U32PGP-E

Page 1: ...nit which may result in injury Electrical work must be performed by a qualified electrician in accordance with the Installation Manual Make sure the air conditioner uses an exclusive power supply The capacity shortage of the power circuit or improper electrical work may result in electric shock or fire Connect the specified wires firmly and clamp them securely so that external force applied to the...

Page 2: ...etaching air intake grille Air intake grille Ceiling panel Adjust corner cap Knobs of air intake grille hooks 2 Safety strap hook Ceiling panel hook hole Hinges 1 Knob Adjust corner cap Adjust corner cap Strap Ceiling panel Open Keep the bracket open Closed Panel fixing bracket Open Close Fig 1 Fig 2 1 Slide the knobs of the hooks of the air intake grille in the direction of arrow 1 and open the g...

Page 3: ...r the four panel fixing brackets Slide the panel fixing bracket while keeping the screw head lower than the bracket The panel fixing screws have been attached to the indoor unit since its shipping 3 Tighten the four panel fixing screws to secure the ceiling panel until it comes into close contact with the indoor unit Fig 5 4 Check that the ceiling panel is in close contact with the ceiling Make su...

Page 4: ...is installed at another location it may cause malfunction of the Kit Attaching adjust corner caps Hook the strap of the adjust corner cap securely to the pin of the ceiling panel Pin Claws A insert to fit Claws B press to fit Insert the two claws A of the adjust corner cap into the rectangular holes of the ceiling panel in the direction of arrow Press the adjust corner cap so that the three claws ...

Reviews: