1. SPECIFICATIONS
1-1. Outdoor Unit
<Super Digital Inverter>
Model name
Outdoor unit
RAV-SP
404ATP
*
454ATP
*
564ATP
*
804ATP
*
Power supply
1 phase 220-240V 50Hz
(Power exclusive to outdoor is required.)
Compressor
Type
Hermetic compressor
Motor
(kW)
1.1 1.1 1.1 1.1
Pole
4
4
4
4
Refrigerant
charged
(kg)
1.0 1.0 1.4
2.1
Refrigerant control
Pulse motor valve
Inter
connecting
pipe
Standard length
(m)
7.5
7.5
7.5
7.5
Min. length
(m)
5
5
5
5
Max. total length
(m)
30
30
50
50
Additional refrigerant charge
under long piping connector
20g/m
(21m to 30m)
20g/m
(21m to 30m)
40g/m
(21m to 50m)
40g/m
(31m to 50m)
Height
difference
Outdoor lower
(m)
30
30
30
30
Outdoor higher
(m)
30
30
30
30
Outer
dimension
Height (mm)
550
550
550
890
Width (mm)
780
780
780
900
Depth (mm)
290
290
290
320
Appearance
Silky shade (Muncel 1Y8.5/0.5)
Total weight
(kg)
40
40
44
63
Heat exchanger
Finned tube
Fan unit
Fan
Propeller fan
Standard air flow high
(m
3
/min.)
40
40
40
50
Motor (W)
43
43
43
63
Connecting
pipe
Gas side
(mm)
12.7
12.7
12.7
15.9
Liquid side
(mm)
6.4
6.4
6.4
9.5
Sound pressure level
Cooling/Heating (dB
·
A)
45/47
45/47
47/48
48/49
Sound power level
Cooling/Heating (dB
·
A)
62/64
62/64
63/64
64/65
Outside air temperature, Cooling
(°C)
43 to -15
Outside air temperature, Heating
(°C)
15 to -15
15 to -20