– 54 –
DN
01
02
03
06
OF
10
11
12
13
14
1E
28
2b
31
32
40
60
Item
Filter sign lighting time
Filter pollution leve
Central control address
Heating suction temperature shift
Cooling only
Type
Indoor unit capacity
System address
Indoor unit address
Group address
Temperature range of cooling/heating
automatic SW control point
Power failure automatic recovery
Thermo output SW (T10
)
Ventilation fan (standalone)
Sensor SW (Selection of static pressure)
Humidifier control (+ drain pump control)
Timer setting (wired remote controller)
Setting data
Factory-set value
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
0003: 3 deg (Ts ± 1.5)
0000: None
0000: Thermo ON
0000: Not available
0000: Body sensor
0003: Humidifier ON + Pump OFF
0000: Available
Table 2. Type: CODE No. 10
Table 3. Indoor unit capacity: CODE No. 11
∗
EEPROM initial value on the P.C. board for indoor unit servicing.
Setting data
0006
Type
Concealed Duct High Static Type
Type name abb.
RAV-SM
∗∗∗
DT-E (TR)
Setting data
0000
∗
0021
0023
Type
Disable
224
280
Table 1