– 77 –
A
B
A
B
Terminal block for remote controller
wiring of indoor unit
Terminal block
Remote controller
unit
Remote controller wire
(Procured locally)
10-3. Remote Controller Wiring
• Strip off approx. 9 mm the wire to be connected.
• For single system, use non polarity, 2 core wire is
used for wiring of the remote controller.
(0.5 mm² to 2.0 mm² wires)
• For the synchronous twin, triple system, use
2-conre shield wire (Vinyl cord for microphone 0.5
to 2.0 mm²) to conform to the EMC standard.
∗
For details of wiring/installation of the remote
controller, refer to the Installation Manual enclosed
with the remote controller.
Single system
Wiring diagram
Simultaneous twin system
A
B
1
1
L
N
2
2
3
3
Power supply
Remote controller
Remote controller wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
A
B
1
1
L
N
2
2
3
3
Power supply
Remote controller
Remote controller wiring
Indoor side
Indoor/Outdoor
connecting wires
Outdoor side
(Example of 2-lines cabling)
(Real line: Cabling, Broken line: Refrigerant pipe)
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit cable.
Group address
Individual :
0000
Master
unit
:
0001
Sub
unit :
0002
In case of group control
Outdoor
Indoor
A B
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
Indoor
A B
1 2 3
1 2 3
Outdoor
1 2 3
Remote controller
Line address
→
1
Indoor unit address
→
1
Group address
→
1
1
2
2
2
1
2
2
2
2
10-4. Address Setup
(Manual setting from remote controller)
In case that addresses of the indoor units will be
determined prior to piping work after cabling work
• Set an indoor unit per a remote controller.
• Turn on power supply.