– 17 –
8
Applicable controls
• For using the wired remote controller RBC-AMS55E ,
refer to the Owner’s Manual attached to the wired
remote controller.
REQUIREMENT
• When you use this air conditioner for the first time, it
takes approx. 5 minutes until the remote controller
becomes available after power-on. This is normal.
<When power is turned on for the first time after
installation>
It takes
approx. 5 minutes
until the remote controller
becomes available.
<When power is turned on for the second (or later)
time>
It takes
approx. 1 minute
until the remote controller
becomes available.
• Normal settings were made when the indoor unit was
shipped from factory.
Change the indoor unit settings as required.
• Use the wired remote controller to change the
settings.
* The settings cannot be changed using the
wireless remote controller, sub remote controller,
or remote-controller-less system (for central
remote controller only). Therefore, install the
wired remote controller to change the settings.
Applicable controls setup
(settings at the site)
Remote controller model name:
RBC-ASCU1
Basic procedure
Be sure to stop the air conditioner before making
settings.
(Change the setup while the air conditioner is not
working.)
CAUTION
CAUTION
Set only the Code No. shown in the following table: Do
NOT set any other Code No.
If a Code No. not listed is set, it may not be possible to
operate the air conditioner or other trouble with the
product may result.
1
Push and hold menu button and [
] setting
button simultaneously for 10 seconds or
more.
• After a while, the display flashes as shown in the
figure. “ALL” is displayed as indoor unit numbers
during initial communication immediately after the
power has been turned on.
Power on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 5 minutes
Power on
“SETTING”
flashes
“SETTING”
goes out
Remote
controller is
available
Approx. 1 minutes
3,6
4,5 1
7
2,4,5
Indoor unit No.
2
Each time [
] [
] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs and the
louvers start swinging. The indoor unit can be
confirmed for which to change settings.
3
Push OFF timer button to confirm the
selected indoor unit.
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
] with [
]
[
] setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
]
with [
] [
] setting button.
6
Push OFF timer button to complete the set
up.
• To change other settings of the selected indoor
unit, repeat from Procedure
4
.
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode)
“
” flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while “
” is flashing.)
• To change settings of another indoor unit,
repeat from Procedure
1
.
Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
(
1
→
2
→
3
→
4
→
5
→
6
→
7
).
• Specify
[5d]
for the Code No. in Procedure
4
.
• Select the set data for Procedure
5
from the “Height
list of ceiling possible to be installed” table in this
manual.
Remote controller-less setting
Change the high-ceiling setting with the DIP switch on
the P.C. board.
* Once the Set data has been changed, though it can
be freely set to “
0001
” or “
0003
”, to reset it to “
0000
”
(factory default), it need changing using remote
controller (sold separately). After set data change,
an air conditioner is operated. After setting has been
completed, restart the air conditioner.
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
the data of Code No.
[5d]
to “
0000
”.
Set data
Code No.
Set data
Ceiling height
0000
Standard
(Factory default)
0001
High ceiling (1)
0003
High ceiling (3)
Set data
Ceiling height
SW501-1 SW501-2
0000
Standard
(Factory default)
OFF
OFF
0001
High ceiling (1)
ON
OFF
0003
High ceiling (3)
OFF
ON
SW501-2
SW501-1
MCU
(IC501)
33-EN
34-EN