Toshiba RAV-HM1101FT-E Installation Manual Download Page 6

– 5 –

Selection of installation location

• When the air conditioner is installed in a small room, provide 

appropriate measures to ensure that the concentration of refrigerant 

leakage occur in the room does not exceed the critical level.

• Do not install in a location where flammable gas leaks are possible. If 

the gas leak and accumulate around the unit, it may ignite and cause 

a fire.

• To transport the air conditioner, wear shoes with additional protective 

toecap.

• To transport the air conditioner, do not take hold of the bands around 

the packing carton. You may injure yourself if the bands should break.

• Do not place any combustion appliance in a place where it is directly 

exposed to the wind of air conditioner, otherwise it may cause 

imperfect combustion.

• Pay attention to the floor area in the room to be installed. The unit 

cannot be installed in the room with floor area less than minimum floor 

area described in Appendix of this Installation Manual.

Installation

• Install the air conditioner securely in a location where the base can 

sustain the weight adequately. If the strength is not enough, the unit 

may fall down resulting in injury.

• Follow the instructions in the Installation Manual to install the air 

conditioner. Failure to follow these instructions may cause the 

product to fall down or topple over or give rise to noise, vibration, 

water leakage or other trouble.

• Carry out the specified installation work to guard against the 

possibility of high winds and earthquake. If the air conditioner is not 

installed appropriately, a unit may topple over or fall down, causing an 

accident.

• If refrigerant gas has leaked during the installation work, ventilate the 

room immediately. If the leaked refrigerant gas comes in contact with 

fire, noxious gas may be generated, which may catch a fire.

• Use forklift to carry in the air conditioner units and use winch or hoist 

at installation of them.

• The installation of pipe work shall be kept to a minimum.

Refrigerant piping

• Install the refrigerant pipe securely during the installation work before 

operating the air conditioner. If the compressor is operated with the 

valve open and without refrigerant pipe, the compressor sucks air and 

the refrigeration cycles is over pressurized, which may cause an 

injury.

• Tighten the flare nut with a torque wrench in the specified manner. 

Excessive tighten of the flare nut may cause a crack in the flare nut 

after a long period, which may result in refrigerant leakage.

• After the installation work, confirm that refrigerant gas does not leak. 

If refrigerant gas leaks into the room and flows near a fire source, 

such as a cooking range, noxious gas may be generated, which may 

catch a fire.

• When the air conditioner has been installed or relocated, follow the 

instructions in the Installation Manual and purge the air completely so 

that no gases other than the refrigerant will be mixed in the 

refrigerating cycle. Failure to purge the air completely may cause the 

air conditioner to malfunction.

• Nitrogen gas must be used for the airtight test.

• The charge hose must be connected in such a way that it is not slack.

Electrical wiring

• Only a Qualified installer (*1) or Qualified service person (*1) is 

allowed to carry out the electrical work of the air conditioner. Under 

no circumstances must this work be done by an unqualified individual 

since failure to carry out the work properly may result in electric 

shocks and/or electrical leaks.

• To connect the electrical wires, repair the electrical parts or undertake 

other electrical jobs, wear gloves to provide protection for electricians 

insulating shoes and clothing to provide protection from electric 

shocks. Failure to wear this protective gear may result in electric 

shocks.

• Use wiring that meets the specifications in the Installation Manual and 

the stipulations in the local regulations and laws. Use of wiring which 

does not meet the specifications may give rise to electric shocks, 

electrical leakage, smoking and/or a fire.

• Connect earth wire. (Grounding work) 

Incomplete earthing causes an electric shock.

• Do not connect earth wires to gas pipes, water pipes, and lightning 

conductor or telephone earth wires.

• After completing the repair or relocation work, check that the earth 

wires are connected properly.

• Install a circuit breaker that meets the specifications in the Installation 

Manual and the stipulations in the local regulations and laws.

• Install the circuit breaker where it can be easily accessed by the 

agent.

• When installing the circuit breaker outdoors, install one which is 

designed to be used outdoors.

9-EN

10-EN

Summary of Contents for RAV-HM1101FT-E

Page 1: ... CONDITIONER SPLIT TYPE Installation Manual R32 Indoor Unit Floor Standing type RAV HM561FT E RAV HM801FT E RAV HM901FT E RAV HM1101FT E RAV HM1401FT E RAV HM1601FT E Model name For commercial use English ...

Page 2: ...rant HFC R32 which does not destroy the ozone layer This indoor unit is for the R32 refrigerant Be sure to combine with an outdoor unit for the R32 refrigerant Product information of ecodesign requirements Regulation EU 2016 2281 http ecodesign toshiba airconditioning eu en Contents 1 Precautions for safety 4 2 Accessory parts 8 3 Selection of installation place 8 4 Installation 10 5 Drain piping ...

Page 3: ... Qualified service person 1 The qualified service person is a person who installs repairs maintains relocates and removes the air conditioners made by Toshiba Carrier Corporation He or she has been trained to install repair maintain relocate and remove the air conditioners made by Toshiba Carrier Corporation or alternatively he or she has been instructed in such operations by an individual or indi...

Page 4: ... or loss of life if the product is handled improperly Text set off in this manner indicates that failure to adhere to the directions in the caution could result in slight injury 2 or damage 3 to property if the product is handled improperly WARNING Risk of fire Read the OWNER S MANUAL carefully before operation Service personnel are required to carefully read the OWNER S MANUAL and INSTALLATION MA...

Page 5: ...d for some reason first put on protective gloves and safety work clothing and then proceed WARNING When work is performed at heights use a ladder which complies with the ISO 14122 standard and follow the procedure in the ladder s instructions Also wear a helmet for use in industry as protective gear to undertake the work This unit is equipped with a refrigerant leak detection sensor for safety to ...

Page 6: ... and the refrigeration cycles is over pressurized which may cause an injury Tighten the flare nut with a torque wrench in the specified manner Excessive tighten of the flare nut may cause a crack in the flare nut after a long period which may result in refrigerant leakage After the installation work confirm that refrigerant gas does not leak If refrigerant gas leaks into the room and flows near a ...

Page 7: ... the air conditioner in the trouble status may cause mechanical problems to escalate or result in electric shocks or other trouble After the work has finished use an insulation tester set 500 V Megger to check the resistance is 1 MΩ or more between the charge section and the non charge metal section Earth section If the resistance value is low a disaster such as a leak or electric shock is caused ...

Page 8: ...tallation work A special tool for the R32 refrigerant is required for installation Use a new and clean piping materials for the connecting pipe so that moisture and dirt are not mixed together during the installation work When using existing pipes follow the Installation Manual enclosed with the outdoor unit Be careful of fan operation when the circuit breaker is turned on If the refrigerant leak ...

Page 9: ...d places where the exhaust air from combustion appliances will be sucked into the unit Doing so may cause the heat exchanger its aluminum fins and copper pipes and other parts to become corroded Locations with atmospheres with mist of cutting oil or other types of machine oil Doing so may cause the heat exchanger to become corroded mists caused by the blockage of the heat exchanger to be generated...

Page 10: ...sulator to the side face and the rear side of the indoor unit 200 or more 500 or more 1000 or more Front side In case of right direction piping Front side To open the intake grille Direction of vertical louver The intake grille is fixed by the screws for safety reasons Use a screwdriver to unfasten the screws of the intake grille two places to open the intake grille The screws are designed to stay...

Page 11: ...ther material not to damage the unit Carry the package by four or more persons and do not bundle it with plastic band at positions other than specified Be sure to take measures to prevent falling at the wall surface and the floor and fix it surely considering prevention of accident of falling because this unit is formed into a thin type If it is not fixed a falling accident may occur After carryin...

Page 12: ... Height of head of fixing bolt Model A B HM56 to HM80 type 88 30 to 80 HM90 to HM160 type 258 40 to 90 A B Wooden wall Screws for side plate Concrete wall Screws bolts Total 4 at right and left Screws for side plate Anchor bolts Total 4 at right and left 634 mm Air intake grille Bracket for fixing to floor Bracket for fixing to wall Electrical control box cover Installation of wired remote control...

Page 13: ... the Cover kit TCB CKC1F E sold separately Follow the steps below to install the Cover kit 1 Removing the remote controller panel 1 Untie the cords of the air inlet grille and remove the air inlet grille 2 Unfasten the two screws fastening the upper cabinet Lift up the upper cabinet and remove it 3 Unfasten the two screws fastened on the back of the upper cabinet and remove the foam cover 4 Push o...

Page 14: ...e in the drain hose and water leakage in the room NOTE The drain pipe and drain hose must be sloping downward at an angle of 1 100 or more and do not run the pipe up and down arched shape or allow it to form traps Be sure to connect the drain hose and drain pipe at the outside of unit and fix them If clearance occurs between piping wiring and drain hose in opening the knockout hole apply putty to ...

Page 15: ...l be hard to remove the drip proof cover and the electrical control box cannot be taken out Drain hose Drain pan Heat insulator Hard polyvinyl chloride pipe Adhesion for hard polyvinyl chloride pipe used To connect drain hose on right or left route it through the knock out for refrigerant piping on HM56 to HM80 model Wiring port both sides Refrigerant pipe connecting port both sides Piping port at...

Page 16: ...hat there are no chips adhered or other problems after flare processing Do not apply refrigerating machine oil to the flare surface Model name RAV HM56 type HM80 HM90 to HM160 type Pipe size Gas side 12 7 mm 15 9 mm Liquid side 6 4 mm 9 5 mm Outer dia of copper pipe R32 tool used Conventional tool used 6 4 9 5 0 0 5 1 0 1 5 12 7 15 9 Outer dia of copper pipe A 0 0 4 6 4 9 1 9 5 13 2 12 7 16 6 15 9...

Page 17: ...e may give rise to smoking and or a fire CAUTION For power supply specifications follow the Installation Manual of outdoor unit Do not connect 220 240 V power to the terminal blocks for control wiring Otherwise the system will fail Do not damage or scratch the conductive core and inner insulator of power and system interconnection wires during peeling them Perform the electric wiring so that it do...

Page 18: ...iring connections between the indoor and outdoor units and between the indoor units and remote controller The wires indicated by the broken lines are provided at the locally 2 Refer to the both indoor and outdoor unit wiring diagrams 3 For details refer to the Installation Manual for outdoor unit to be connected Wiring diagram Example Use 2 core shield wire MVVS 0 5 to 2 0 mm or more for the remot...

Page 19: ... figure Do not apply tension on the connecting part of the terminal block Be sure to mount cover of the electrical control box and the drip proof cover 1 3 4 2 Drip proof cover HM56 to HM80 only Electrical control box cover Electrical control box A B Positioning of hole for wiring Knock out hole HM56 HM80 HM90 to HM160 Wiring hole Knock out hole Wiring hole Knock out hole Earth screw Indoor and ou...

Page 20: ...buttons for more than 4 seconds Power on Setting flashes Setting goes out Remote controller is available Approx 5 minutes Power on Setting flashes Setting goes out Remote controller is available Approx 1 minutes 6 Setting timer operation mode 7 DN setting 8 Reset power consumption data 9 Notice history Field setting menu 2 2 Return Set 3 Push the button to select 7 DN setting on the Field setting ...

Page 21: ...he basic operation procedure 1 2 3 4 5 For the Code DN in Procedure 3 specify 00FC For the Data in Procedure 3 select the Data 0000 TCC Link Data Filter sign term 0000 None 0001 150 H Factory default 0002 2500 H 0003 5000 H 0004 10000 H Data Detection temperature shift value 0000 No shift Factory default 0001 1 C 0002 2 C 0003 3 C 0004 4 C 0005 5 C 0006 6 C Data 8 C Operation setting 0000 None Fac...

Page 22: ...n system Triple system Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Indoor unit Outdoor unit Finish of address setup by power ON Remote controller Indoor unit Indoor unit Indoor unit Indoor unit Group control for system of multiple units One group can control up ...

Page 23: ...ess 3 2 2 Address 3 3 2 Address 3 1 2 Address 2 2 2 Address 1 2 2 Procedure example Manual address setup procedure While the operation stops change the setup Stop the operation of the unit Address is displayed here 1 Push the MENU button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more th...

Page 24: ...stance of less than 1 MΩ is detected do not run the unit 2 Check the valve of the outdoor unit being opened fully To protect the compressor at activation time leave power ON for 12 hours or more before operating Execute a test run Operate the unit with the remote controller as usual For the procedure of the operation refer to the attached Owner s Manual A forced test run can be executed in the fol...

Page 25: ... to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu Push and hold the buttons for more than 4 seconds 3 Push the button to select 4 Monitor function on the Field setting menu screen then push the Set F2 button Push the button to select the code to check data 4 Push the CANCEL button to return to the Field setting menu screen...

Page 26: ...itioner when filter sign appears on the detailed display Push one of the operation buttons to erase the message or wait for more than 5 seconds until the message disappears Cool 24 Room A 12 00 Mode Fan Speed Filter sign Filter check Room A 12 00 Mode Fan Speed 1 Push the ON OFF button to stop the operation then turn off the circuit breaker 2 Use a screwdriver to unfasten the screws of the intake ...

Page 27: ...if there are any waggles damages or adhesive dust Filter Go to installed location and check if there are any stains or breaks on the filter Drain pan Access from inspection opening and remove the access panel Check if there is any clogging or drain water is polluted Refrigerant leak detection sensor Open the intake grille and E BOX and check if there are any troubles on sensor s appearance or its ...

Page 28: ...was detected Auto reset E09 Duplicated header remote controllers Remote controller Remote controller address setting trouble Two remote controllers are set as header in the double remote controller control The header indoor unit stops raising alarm and follower indoor units continue to operate E10 CPU CPU communication trouble Indoor Indoor P C board Communication trouble between main MCU and moto...

Page 29: ...e to incorrect external input into CN80 Entire stop L31 SIM Phase sequence trouble etc Outdoor Power supply phase sequence outdoor unit P C board Abnormal phase sequence of the 3 phase power supply Operation continued thermos tat OFF Remote controller display Wireless remote controller Sensor block display of receiving unit Main defective parts Judging device Parts to be checked trouble descriptio...

Page 30: ...90 14 86 1 80 6 00 15 11 1 84 4 64 6 10 15 36 1 90 4 79 6 20 15 62 2 00 5 04 6 30 15 87 2 10 5 29 6 40 16 12 2 20 5 54 6 50 16 37 2 30 5 80 6 60 16 62 2 40 6 05 6 70 16 87 2 50 6 30 6 80 17 13 2 60 6 55 6 90 17 38 2 70 6 80 7 00 17 63 2 80 7 05 7 10 17 88 2 90 7 31 7 20 18 13 3 00 7 56 7 30 18 38 3 10 7 81 7 40 18 64 3 20 8 06 7 50 18 89 3 30 8 31 7 60 19 14 3 40 8 57 7 70 19 39 3 50 8 82 7 80 19 ...

Page 31: ...EB99847901 DH91308301 ...

Reviews: