
Error mode detected by indoor unit
Operation of diagnostic function
Check
code
E03
E04
E08
L03
L07
L08
L09
L30
P10
P12
P19
P31
F01
F02
F10
F29
E10
Cause of errors
No communication from remote
controller (including wireless) and
communication adapter
indoor P.C. board
Duplicated indoor unit address
Duplicated indoor master unit
There is group wire in individual indoor
unit.
Unset indoor group address
Unset indoor capacity
Abnormal input of outside interlock
Float switch operation
Float circuit, Disconnection,
Coming-off, Float switch contact error
Indoor DC fan error
4-way valve system error
•
Own unit stops while warning is output
to other indoor units.
Coming-off, disconnection or short of
indoor heat exchanger temp. sensor
(TCJ)
Coming-off, disconnection or short of
indoor heat exchanger temp. sensor
(TC)
Coming-off, disconnection or short of
indoor heat exchanger temp. sensor
(TA)
Indoor EEPROM error
Communication error between indoor
MCU
Communication error between fan
driving MCU and main MCU
Status of
air conditioner
Stop
Stop
Stop
Stop
Stop
Condition
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Displayed when
error is detected
Judgment and measures
Remote controller LCD display OFF (Disconnection)
Central remote controller [97] check code
1. Check whether remote controller connection (Group/Individual)
was changed or not after power supply turned on
(Finish of group construction/Address check).
* If group construction and address are not normal when the
power has been turned on, the mode automatically shifts to
address setup mode. (Resetting of address)
1. Set indoor capacity (CODE No. (DN) = 11)
1. Check outside devices.
2. Check indoor P.C. board.
1. Trouble of drain pump
2. Clogging of drain pump
3. Check float switch.
4.
5. Check Application control kit of indoor unit
Check indoor P.C. board.
1. Position detection error
2. Over-current protective circuit of indoor fan driving unit operated.
3. Indoor fan locked.
4. Check indoor P.C. board.
1. Check 4-way valve.
2. Check PMV
3. Check indoor heat exchanger (TC/TCJ).
4. Check indoor P.C. board.
1. Judge follower unit while header unit is [E03], [L03], [L07] or [L08].
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TCJ).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TC).
2. Check indoor P.C. board.
1. Check indoor heat exchanger temp. sensor (TA)
TT .
2. Check indoor P.C. board.
1. Check indoor EEPROM. (including socket insertion)
2. Check indoor P.C. board.
1. Check indoor P.C. board.
1. Check power supply / communication harness
2. Check indoor P.C. board
E18
Regular communication error between
indoor master and follower units and
between main and sub units
Displayed when
error is detected
1. Check remote controller wiring.
2. Check indoor power supply wiring.
3. Check indoor P.C. board.
After heating operation has started,
indoor heat exchangers temp. is
down.
1. Outdoor unit does not completely operate.
Inter-unit wire check, correction of misswiring
Check outdoor P.C. board. Correct wiring of P.C. board.
2. When outdoor unit normally operates
Check P.C. board (Indoor receiving / Outdoor sending).
1. Check cables of remote controller and communication adapters.
The serial signal is not output from
outdoor unit to indoor unit.
Miswiring of inter-unit wire
Defective serial sending circuit on
outdoor P.C. board
Defective serial receiving circuit on
E11
Communication error between
Application and indoor unit
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Follower unit)
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
Stop
(Automatically
reset)
EEPROM access error
- 56 -
FILE NO.
SVM-18043
Summary of Contents for RAV-GM1101ATJP-E
Page 21: ...2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM561AT P GM801AT P 21 FILE NO SVM 18043 ...
Page 22: ...2 2 RAV GM1101AT P GM1401AT P 22 FILE NO SVM 18043 ...
Page 28: ...4 WIRING DIAGRAM 4 1 RAV GM561AT P GM801AT P 28 FILE NO SVM 18043 ...
Page 29: ...4 2 RAV GM1101AT P GM1401AT P 29 FILE NO SVM 18043 ...
Page 116: ... Inverter assembly GM56 116 FILE NO SVM 18043 ...
Page 120: ... Inverter assembly GM80 120 FILE NO SVM 18043 ...
Page 124: ... Inverter assembly GM110 140 124 FILE NO SVM 18043 ...