3. Current release control
The output frequency and the output voltage are controlled by AC current value detected by current transformer
on the outdoor P.C. board so that input current of the inverter does not exceed the specified value.
I
1
I
1 – 0.5
Current [A]
Frequency down
Normal operation
Hold
Hold
Model
GM56
GM80
COOL HEAT COOL HEAT
I1 value [A]
10.1
12.0
14.5
14.0
Model
GM110
GM140
COOL HEAT COOL HEAT
I1 value [A]
21.2
21.2
21.2
21.2
4. Outdoor fan control
Allocations of fan tap revolutions [rpm]
Model
W1
W2
W3
W4
W5
W6
W7
W8
W9
WA
WB
WC
WD
WE
WF
GM56
200
300
350
410
480
500
530
560
640
670
700
750
800
840
950
GM80
200
300
350
410
480
500
530
560
640
670
700
750
840
980 1050
GM110
200
210
250
320
390
460
530
600
660
730
770
840
880
930
930
GM140
200
210
250
320
390
460
530
600
660
730
770
840
880
930
930
4-1. Cooling fan control
1) An outdoor fan is controlled by TL sensor, TO sensor and compressor frequency. An outdoor fan is
controlled at 1-tap interval of DC fan control.
2) At the start time, the fan is fixed for 60 seconds only with the maximum fan tap corresponded to the zone
in the following table but it is controlled with TL sensor temperature after then.
+
1 tap / 20 sec (Up to the maximum
rotational frequency of each zone)
Rotational frequency hold
– 1 tap / 20 sec
(Up to the minimum rotational
frequency of each zone)
GM56, 80 : WE tap
GM110, 140 : WD tap
TL
55˚C
38˚C
35˚C
58˚C
Temp.
range
GM56
34.2 Hz or lower 34.2Hz to 58.8Hz 58.8Hz or higher
GM80
46.8 Hz or lower 46.8Hz to 83.4Hz 83.4Hz or higher
Min.
Max.
Min.
Max.
Min.
Max.
38°C
≤
TO
W6
WB
W8
WE
WA
WE
29°C
≤
TO < 38°C
W5
WA
W7
WE
W9
WE
15°C
≤
TO < 29°C
W3
W7
W5
W9
W7
WB
5°C
≤
TO < 15°C
W2
W5
W4
W7
W6
W9
0°C
≤
TO < 5°C
W1
W3
W3
W5
W4
W7
–4°C
≤
TO < 0°C
W1
W2
W2
W4
W3
W5
TO < –4°C
OFF
OFF
OFF
W3
W1
W4
TO error
OFF
WB
OFF
WE
W1
WE
Temp.
range
GM110
GM140
34.2 Hz or lower 34.2Hz to 52.2Hz 52.2Hz or higher
Min.
Max.
Min.
Max.
Min.
Max.
38°C
≤
TO
W6
WD
W8
WD
WA
WD
29°C
≤
TO < 38°C
W5
WC
W7
WC
W9
WD
15°C
≤
TO < 29°C
W3
W7
W5
W9
W7
WB
5°C
≤
TO < 15°C
W2
W5
W4
W7
W6
W9
0°C
≤
TO < 5°C
W1
W3
W3
W5
W4
W7
–4°C
≤
TO < 0°C
W1
W2
W2
W4
W3
W5
TO < –4°C
OFF
W2
OFF
W4
OFF
W4
TO error
OFF
WD
OFF
WD
OFF
WD
- 43 -
FILE NO.
SVM-18043
Summary of Contents for RAV-GM1101ATJP-E
Page 21: ...2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM561AT P GM801AT P 21 FILE NO SVM 18043 ...
Page 22: ...2 2 RAV GM1101AT P GM1401AT P 22 FILE NO SVM 18043 ...
Page 28: ...4 WIRING DIAGRAM 4 1 RAV GM561AT P GM801AT P 28 FILE NO SVM 18043 ...
Page 29: ...4 2 RAV GM1101AT P GM1401AT P 29 FILE NO SVM 18043 ...
Page 116: ... Inverter assembly GM56 116 FILE NO SVM 18043 ...
Page 120: ... Inverter assembly GM80 120 FILE NO SVM 18043 ...
Page 124: ... Inverter assembly GM110 140 124 FILE NO SVM 18043 ...