TD
sensor
TS
sensor
TL sensor
TE
4-way valve
(STF-H0218)
2-step
muffler
Ø25 × 200L
Rotary compressor
(DX150A1T-20F)
Accumulator
(1000cc)
sensor
Heat exchanger
Ø8 ripple, 2 rows,
20 steps
FP1.3 flat fin
PMV
(Pulse Motor Valve)
(DPF(S01)1.8C-15)
R32 : 1.3 kg
Cooling
Heating
Packed valve
Outer dia. Ø15.88
Packed valve
Outer dia. Ø9.52
Muffler
Ø19.05 × 160L
Strainer
RAV-
G
M80
1
AT
P
T
Ō
sensor
P
Pressure
switch
Distributor
Pressure
Pipe surface temperature (°C)
Compressor
revolutions per
second (rps)
*
Indoor
fan
Indoor/Outdoor
temp. conditions
(DB/WB) (°C)
(MPa)
(kg/cm
2
G)
Discharge
(TD)
Suction
(TS)
Indoor heat
exchanger
(TC)
Outdoor heat
exchanger
(TE)
Pd
Ps
Pd
Ps
Indoor
Outdoor
Cooling
Standard
3.27 0.89 33.3 9.1
95
11
10
41
80
HIGH
27/19
35/-
Overload
3.63 1.26 37.0 10.2
80
19
18
51
53
HIGH
32/24
46/-
Low load
1.96 0.85 20.0 8.7
53
4
3
16
72
HIGH
18/15.5
-5/-
Heating
Standard
2.61 0.64 26.6 6.5
88
3
41
1
90
HIGH
20/-
7/6
Overload
3.24 0.94 33.0 9.6
84
13
53
11
76
HIGH
30/-
24/18
Low load
1.76 0.20 17.9 2.0
90
-21
31
-20
120
HIGH
15/-
-15/-
* 4 poles are provided to this compressor.
The compressor frequency (Hz) measured with a clamp meter is 2 times of revolutions (rps) of the compressor.
- 26 -
Muffler
Ø19.05 × 160L
Muffler
Ø19.05
× 160L
Strainer
FILE NO. SVM-18043
Summary of Contents for RAV-GM1101ATJP-E
Page 21: ...2 CONSTRUCTION VIEWS EXTERNAL VIEWS 2 1 RAV GM561AT P GM801AT P 21 FILE NO SVM 18043 ...
Page 22: ...2 2 RAV GM1101AT P GM1401AT P 22 FILE NO SVM 18043 ...
Page 28: ...4 WIRING DIAGRAM 4 1 RAV GM561AT P GM801AT P 28 FILE NO SVM 18043 ...
Page 29: ...4 2 RAV GM1101AT P GM1401AT P 29 FILE NO SVM 18043 ...
Page 116: ... Inverter assembly GM56 116 FILE NO SVM 18043 ...
Page 120: ... Inverter assembly GM80 120 FILE NO SVM 18043 ...
Page 124: ... Inverter assembly GM110 140 124 FILE NO SVM 18043 ...