Toshiba RAS-M05PKVSG-E Installation Manual Download Page 12

10

Drain
guide

Space for pipes

Wall

Shield pipe

Inside the room

Drain hose

Extension drain hose

Arrange the drain pipe for proper drainage from the unit.
Improper drainage can result in dew-dropping.

This air conditioner has the structure designed 
to drain water collected from dew, which forms 
on the back of the indoor unit, to the drain pan. 
Therefore, do not store the power cord and other 
parts at a height above the drain guide.

CAUTION

2.  Put water in the drain pan and make sure that the water is drained out of 

doors.

3. When connecting extension drain hose, insulate the connecting part of 

extension drain hose with shield pipe.

 

NOTE

If the pipe is bent incorrectly, the indoor unit may unstably be set on the wall.
After passing the connecting pipe through the pipe hole, connect the 
connecting pipes to the auxiliary pipes and wrap the facing tape around 
them.

CAUTION

• Bind the auxiliary pipes (two) and connecting cable with facing tape 

tightly. In case of leftward piping and rear-leftward piping, bind the 
auxiliary pipes (two) only with facing tape.

Indoor unit

Connecting cable

Auxiliary pipes

Installation plate

 

•  Carefully arrange pipes so that any pipe does not stick out of the rear 

plate of the indoor unit.

• Carefully connect the auxiliary pipes and connecting pipes to one 

another and cut off the insulating tape wound on the connecting pipe to 
avoid double-taping at the joint; moreover, seal the joint with the vinyl 
tape, etc.

•  Since dewing results in a machine trouble, make sure to insulate both 

connecting pipes. (Use polyethylene foam as insulating material.)

•  When bending a pipe, carefully do it, not to crush it. 

Do not form the
drain hose into
a wavy shape.

Do not rise the
drain hose.

50 mm
or more

Do not put the
drain hose end
into water.

Do not put the
drain hose end
in the drainage ditch.

1

2

1

Hook here.

Installation plate

Hook

Press

(unhook)

Push

Push

Indoor Unit Fixing

•  For detaching the indoor unit from 

the installation plate, pull the indoor 
unit toward you while pushing its 
bottom up at the speci

fi

 ed parts.

1.  Pass the pipe through the hole in the wall and hook the indoor unit on the 

installation plate at the upper hook.

2.  Swing the indoor unit to right and left to con

fi

 rm that it is 

fi

 rmly hooked up on 

the installation plate.

3.  While pressing the indoor unit onto the wall, hook it at the lower part on the 

installation plate. Pull the indoor unit toward you to con

fi

 rm that it is 

fi

 rmly 

hooked up on the installation plate.

Drainage

1.  Run the drain hose sloped downwards.

 

NOTE

•  The hole should be made at a slight downward slant on the outdoor side.

Left-hand connection with piping

•  Bend the connecting pipe so that it is laid within 43 mm above the wall 

surface. If the connecting pipe is laid exceeding 43 mm above the wall 
surface, the indoor unit may unstably be set on the wall.

  When bending the connecting pipe, make sure to use a spring bender so 

as not to crush the pipe.

Bend the connecting pipe within a radius of 30 mm.

To connect the pipe after installation of the unit (

fi

 gure)

80

  

260 mm

210 mm

43 mm

Liquid side

Gas side

(To the forefront of 

fl

 are)

Outward form of indoor unit

R 30 mm (Use polisin (polyethylene)

core or the like for bending pipe.)

Use the handle of screwdriver, etc.

In case of bottom right or bottom left piping

•  After scribing slits of the back body 

with a knife or a making-off pin, cut 
them with a pair of nippers or an 
equivalent tool. 

Slit

In case of right or left piping

•  After scribing slits of the back body 

with a knife or a making-off pin, cut 
them with a pair of nippers or an 
equivalent tool. 

Slit

Summary of Contents for RAS-M05PKVSG-E

Page 1: ...AL Indoor unit RAS M05 07PKVSG E 1122950199 R32 ENGLISH ESPAÑOL FRANÇAIS ITALIANO DEUTSCH PORTUGUÊS POLSKI ČESKY PУCСКИЙ HRVATSKI MAGYAR NEDERLANDS ΕΛΛΗΝΙΚΑ SVENSKA SUOMI NORSK DANSK ROMÂNĂ БЪЛГАРСКИ EESTI LATVISKI SLOVENČINA SLOVENŠČINA LIETUVIŲ ...

Page 2: ...lation Place 7 Cutting a Hole and Mounting Installation Plate 7 Wiring Connection 8 How to Connect Remote Controller for Wire Operation 8 Piping and Drain Hose Installation 9 Indoor Unit Fixing 10 Drainage 10 OTHERS 11 Gas Leak Test 11 Remote Control A B Selection 11 Test Operation 11 Auto Restart Setting 11 APPENDIX 12 CONTENTS EN ...

Page 3: ...oes not require admission or repeated hospital treatment 2 Property damage means greater damage which affects assets or resources For general public use Power supply cord and connecting cable of appliance use shall be at least polychloroprene sheathed flexible cord design H07RN F or cord designation 60245 IEC66 Shall be installed in accordance with national wiring regulations This appliance must b...

Page 4: ...ELECTRIC PARTS MAY BE DAMAGED CHECK THE EARTH WIRE THAT IT IS NOT BROKEN OR DISCONNECTED BEFORE INSTALLATION DO NOT INSTALL NEAR CONCENTRATIONS OF COMBUSTIBLE GAS OR GAS VAPORS FAILURE TO FOLLOW THIS INSTRUCTION CAN RESULT IN FIRE OR EXPLOSION TO PREVENT OVERHEATING THE INDOOR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE ...

Page 5: ...d possibly result in explosion and injury Thickness of copper pipes used R32 must be more than 0 8mm Never use copper pipes thinner than 0 8mm Do not perform flare connection inside a building or dwelling or room when joining the heat exchanger of indoor unit with interconnection piping Refrigerant connection inside a building or dwelling or room must be made by brazing or welding Joint connection...

Page 6: ...ater or other moisture before installation could result in electric shock Do not store it in a wet basement or expose to rain or water After unpacking the unit examine it carefully for possible damage Do not install the unit at place where leakage of flammable gas may occur In case gas leaks and accumulates at surrounding of the unit it may cause of fire Do not install in a place that can increase...

Page 7: ...mend to use vacuum to clean by sucking the dusts which stick or dip inside the filter or use the blower to blow the dust go out through the filter 2 If necessary to use water to clean simply use the plain water to wash the filter dry with the sunlight for 3 4 hours or until it completely dry Nevertheless use hair drier to dry it However washing with water it may reduce the performance of the filte...

Page 8: ... holder Wireless remote control Shield pipe Attach to the front panel Air filter Hook Installation plate Hook 65 mm or more 300 mm or more 300 mm or more Insert the cushion between the indoor unit and wall and tilt the indoor unit for better operation For the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole ...

Page 9: ...ed The indoor unit shall be installed at least 2 5 m height Also it must be avoided to put anything on the top of the indoor unit CAUTION 5 4 45 5 7 Side view Top view Indoor unit R e c e p t i o n r a n g e Remote control Remote control Reception range Indoor unit The center of the pipe hole is above the arrow Pipe hole Ø65 mm 120 mm 6 When the installation plate is directly mounted on the wall 1...

Page 10: ...ontrol wire Remote controller How to Connect Remote Controller for Wire Operation For indoor unit Wiring Connection Indoor unit Wiring of the connecting cable can be carried out without removing the front panel 1 Remove the air inlet grille Open the air inlet grille upward and pull it toward you 2 Remove the terminal cover and cord clamp 3 Insert the connecting cable according to the local cords i...

Page 11: ...to initial condition when user shutdown power supply of air conditioner Control wire Hole for hang remote controller Remote controller Control wire Screw Ø3 1 16L for hang remote controller Wall Screw Ø3 1 25L for fix battery cover Remote controller 8 9 Battery cover Screw Tighten firmly but not over 0 15 N m 0 02 kgf m 1 Remove cover of remote controller by sliding down and take it out 2 If batte...

Page 12: ...rise the drain hose 50 mm or more Do not put the drain hose end into water Do not put the drain hose end in the drainage ditch 1 2 1 Hook here Installation plate Hook Press unhook Push Push Indoor Unit Fixing For detaching the indoor unit from the installation plate pull the indoor unit toward you while pushing its bottom up at the specified parts 1 Pass the pipe through the hole in the wall and h...

Page 13: ...the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B setting and A room B room when connecting the piping and c...

Page 14: ...il a large quantity of residue shiny metal dust or other wear residue or mixture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel f...

Reviews: