-5. How to set the SERVICE SWITCH SETTING.
If you want to set the "COOLING ONLY SETTING OFF ⇒ ON" .
○:ON, ●:OFF, ◎:Rapid Flashing(5 times/sec), ◇:Slow Flashing(1 time/sec)
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
●
●
●
●
●
●
Push SW
8
01
Hold time
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
●
●
●
●
●
●
Service support function display starts
t≥5 sec ?
Yes
Service switch setting display starts
No
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
●
●
●
◇
●
Initial status
Push SW
8
01 &
SW8
02
at the same time
for
5 sec or more
Turn on the circuit breaker
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
○
○
○
○
●
Push SW
8
02
1 time
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
○
○
○
○
●
Hold time
t≥5 sec ?
Push SW
8
02
Yes
No
D800
D801
D802
D803
D804
D805
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Yellow)
(Green)
○
○
○
○
○
●
Function item
"Cooling only setting"
Setting "OFF"
(Factory setting)
Setting "ON"
Setting completion
Refer to 9-
3
-6.
Push SW
8
01
7 times
●
○
●
●
◎
●
◎
◎
◎
◇
○
FILE NO. SVM-18051