13
Outdoor Unit
Installation Manual
Wire Connection
• The dash lines show on-site wiring.
For indoor unit RAS-M series.
2
L
N
3
1
2
3
(Main circuit)
(System
interconnection wires)
Remote
controller
Indoor unit
Earth
Leakage
breaker
Input power
For indoor unit RAS-B series.
2
L
N
3
2
3
(Main circuit)
(System
interconnection wires)
Remote
controller
Indoor unit
Earth
Leakage
breaker
Input power
• Connect the indoor/outdoor connecting cables to the identical terminal
numbers on the terminal block of each unit.
• Incorrect connection may cause a failure.
Model
RAS-2M10U2AVG-E
RAS-2M14U2AVG-E
RAS-2M18U2AVG-E
RAS-3M18U2AVG-E
Power supply
1ph, 50Hz, 220-240V
Maximum running
current
12.3A
12.6A
13.1A
Installation fuse
rating
15A
(All types can be used)
Power cord
H07RN-F or 60245 IEC 66
3-core 1.5 mm²
Connecting cable
H07RN-F or 60245 IEC 66
4-core 1.0 mm²
1. Remove the valve cover screws.
2. Pull the valve cover in the direction of arrow, and remove it.
3. Remove the cord clamp and the terminal cover.
Valve cover
Terminal cover
Cord clamp
4. Connect the wires for the power source and each indoor unit.
• Connect the connecting cable to the terminal as identi
fi
ed by the
matching numbers on the terminal block of the indoor and the outdoor
unit.
5. Fix the wiring connections for the power source and each indoor unit
securely using a cord clamp.
6. Attach the terminal cover and the valve cover.
Stripping Length of connecting cable for outdoor unit
55
5
5
30
1(L)
2 3
5
5
30
55
L N
Earth screw
Earth screw
Power cord
Connecting cable
Unit A
Earth screw
Earth screw
Connecting cable
Unit C
Connecting cable
Unit B
Earth wire
Earth wire
Connecting cable
Power cord
8
Grounding
This air conditioner must be grounded without fail.
• Grounding is necessary not only to safeguard against the possibility
of receiving an electric shock but also to absorb both static, which is
generated by high frequencies and held in the surface of the outdoor unit,
and noise since the air conditioner incorporates a frequency conversion
device (called an inverter) in the outdoor unit.
• If the air conditioner is not grounded, users may receive an electric shock
if they touch the surface of the outdoor unit and that unit is charged with
static.
9
Test run
Wiring/Piping Check
CAUTION
Electric current is applied on the
control board. Beware of electric
shock.
1. Remove the valve cover screws.
2. Pull the valve cover in the direction of arrow, and remove it.
SW01
SW02
D800
D801
D802
D803
D804
D805
Valve cover
LED
Service switches