Toshiba RAS-2M10U2AVG-E Installation Manual Download Page 12

11

Outdoor Unit

Installation Manual

6

Refrigerant piping

CAUTION

Install in rooms that are 5 m

3

 or larger. If 

a leak of refrigerant gas occurs inside the 
room, an oxygen de

fi

 ciency may occur.

„

Detaching the Valve cover

Remove the 5 screws.

•  Pull the valve cover in the direction of the arrow, and remove it.

Valve cover

„

Refrigerant Piping Connection

Flaring

1. Cut the pipe with a pipe cutter.

90°

Obliquity

Roughness

Warp

2. Remove the burr inside of the pipe.
  When removing the burr, be careful so that chips do not fall into the pipe.
3. Remove the 

fl

 are nuts attached to the outdoor/indoor unit, then insert them 

into each of the pipes.

4. Flare the pipes.
  See the following table for the projection margin (A) and 

fl

 aring size (B)

B

A

Die

Pipe

Pipe

A

B

Flare Nut

Outside 

diameter

Thickness

Rigid 

(clutch 

type) 

R32 tool

Imperial 

(wing 

nut type) 

R32 tool

Width 

across 

fl

 at

Tighten torque

mm

mm

mm

mm

mm

mm

N•m

kgf•m

6.35

0.8

0 to 0.5

1.5 to 

2.0

9.1

17

14 to 

18

1.4 to 

1.8

9.52

0.8

0 to 0.5

1.5 to 

2.0

13.2

22

33 to 

42

3.3 to 

4.2

12.7

0.8

0 to 0.5

2.0 to 

2.5

16.6

26

50 to 

62

5.0 to 

6.2

CAUTION

•  Do not scratch the inner surface of the 

fl

 ared part when removing burrs.

•  Flare processing under the condition of 

scratches on the inner surface of 

fl

 are 

processing part will cause refrigerant gas 
leak.

Pipe connection

1. Make wire and pipe connections for each indoor unit separately.
2. Align the centres of the connecting pipes and tighten the 

fl

 are nut as much 

as possible with your 

fi

 ngers, then tighten the nut using a torque wrench.

  Be sure to tighten the nut at the speci

fi

 ed torque value.

•  If you use one outdoor unit for several indoor units of a different class, 

connect the largest one 

fi

 rst A, then connect the rest in the order B to C.

•  Do not remove the 

fl

 are nuts for any ports you are not going to use for 

connection.

•  Do not leave the 

fl

 are nut unattached for a long period of time.

•  Use a different-diameter joint if the diameters of the connection port and 

connection piping are different.

•  Mount the different-diameter joint on the connection port of the outdoor 

unit.

CAUTION

• 

KEEP IMPORTANT 6 POINTS FOR 
PIPING WORK.

(1)  Take away dust and moisture (inside 

of the connecting pipes).

(2)  Tighten the connections (between 

pipes and unit).

(3)  Evacuate the air in the connecting 

pipes using a VACUUM PUMP.

(4)  Check gas leak (connected points).
(5)  Be sure to fully open the packed 

valves before operation.

(6)  Reusable mechanical connectors 

and 

fl

 ared joints are not allowed 

indoors. When mechanical 
connectors are reused indoors, 
sealing parts shall be renewed. 
When 

fl

 ared joints are reused 

indoors, the 

fl

 are part shall be 

refabricated.

„

Air Purge

From the sake of environmental protection, use a vacuum pump to extract the 
air during installation.
* Prepare a 4 mm hexagon wrench.
1. Connect a charge hose.

•  Make sure that the Handle Hi of the gauge manifold valve is closed fully.
•  Connect the port of the gauge manifold valve and the service port 

(Valve core (Setting Pin)) using the charge hose.

NOTE

If a control valve or charge valve is attached to the charge hose, leak 
of R32 refrigerant can be avoided.

2. Open the Handle Low of the gauge manifold valve fully, then operate the 

vacuum pump.
• Loosen 

the 

fl

 are nut of the at the gas end a little to make sure that air is 

taken in, then tighten the nut.

• If 

you 

fi

 nd air is not taken in, make sure that the charge hose is 

connected to the port(s) securely.

•  Perform extraction for about 15 or more minutes and make sure that the 

compound pressure gauge reading is –101 kPa (–76 cmHg).

•  If the compound pressure gauge reading is not –101 kPa (–76 cmHg), 

there is a possibility air is being taken in from the port(s).

•  Make sure that the charge hose is connected to the port(s) securely.

3. Close the Handle Low of the gauge manifold valve fully, then stop 

operating the vacuum pump.
•  Leave the gauge and pump as they are for 1 or 2 minutes, then make 

sure that the compound pressure gauge reading stays at –101 kPa (–76 
cmHg).

•  You need not add refrigerant.

Summary of Contents for RAS-2M10U2AVG-E

Page 1: ...oor Unit AIR CONDITIONER MULTI SPLIT TYPE Model name RAS 2M10U2AVG E RAS 2M14U2AVG E RAS 2M18U2AVG E RAS 3M18U2AVG E NOTE Descriptions about operations for the 3 indoor units in this manual are not applicable to RAS 2M10U2AVG E RAS 2M14U2AVG E and RAS 2M18U2AVG E R32 ...

Page 2: ...9 Test run 13 10 Pump down Operation 15 11 Troubleshooting 15 12 Appendix 16 Please read this Installation Manual carefully before installing the Air Conditioner This Manual describes the installation method of the outdoor unit For installation of the indoor unit refer to the Installation Manual attached to the indoor unit IMPORTANT NOTICE For details on how to install the indoor units refer to th...

Page 3: ...t type is R32 this unit uses a flammable refrigerant If refrigerant leaks and comes in contact with fire or heating part it will create harmful gas and there is risk of fire Read the OWNER S MANUAL carefully before operation Service personnel are required to carefully read the OWNER S MANUAL and INSTALLATION MANUAL before operation Further information is available in the OWNER S MANUAL INSTALLATIO...

Page 4: ... NEW REFRIGERANT AIR CONDITIONER INSTALLATION THIS AIR CONDITIONER USES THE NEW HFC REFRIGERANT R32 WHICH DOES NOT DESTROY THE OZONE LAYER R32 REFRIGERANT IS APT TO BE AFFECTED BY IMPURITIES SUCH AS WATER OXIDIZING MEMBRANES AND OILS BECAUSE THE PRESSURE OF R32 REFRIGERANT IS APPROX 1 6 TIMES OF REFRIGERANT R22 AS WELL AS THE ADOPTION OF THIS NEW REFRIGERANT REFRIGERATING MACHINE OIL HAS ALSO BEEN...

Page 5: ...OR UNIT AND CAUSING A FIRE HAZARD PLACE THE UNIT WELL AWAY MORE THAN 2 M FROM HEAT SOURCES SUCH AS RADIATORS HEATERS FURNACE STOVES ETC WHEN MOVING THE AIR CONDITIONER FOR INSTALLING IT IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R32 WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE R...

Page 6: ...rant inside the unit is flammable If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker it may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer from which you purchased the unit Do not use the unit until a service person confirms that the portion from which the refrig...

Page 7: ...d the manual A dedicated circuit and the rated voltage must be used Insufficient power supply or improper installation may cause electrical shock or fire Use a cabtyre cable to connect wires in the indoor outdoor units Midway connection stranded wire and single wire connections are not allowed Improper connection or fixing may cause a fire Wiring between the indoor unit and outdoor units must be w...

Page 8: ...on failure or excess current resulting in fire or electrical shock If you detect any damage do not install the unit Contact your supplying dealer immediately Never modify this unit by removing any of the safety guards or bypassing any of the safety interlock switches Do not wash air conditioners with pressure washers Electric leaks may cause electric shocks or fires Be sure to comply with local re...

Page 9: ...s for installation work Failure to do so may cause personal injury when handling parts with sharp edges Do not touch the air intake section or the aluminium fins of the outdoor unit It may cause injury Do not install the outdoor unit in a place which can be a nest for small animals Small animals could enter and contact internal electrical parts causing a failure or fire Request the user to keep th...

Page 10: ...the above the safety protection functions may be activated Example of indoor unit class RAS B10UFV E1 is abbreviated as 10 Indoor unit class Standard connecting pipe diameter RAS 2M10U2AVG E RAS 2M14U2AVG E RAS 2M18U2AVG E RAS 3M18U2AVG E Unit C 07 or 10 or 13 6 35 9 52 mm Unit B 07 or 10 or 13 or 16 6 35 9 52 mm 6 35 9 52 mm 6 35 9 52 mm 3 6 35 9 52 mm 3 Unit A 07 or 10 or 13 or 16 6 35 9 52 mm 6...

Page 11: ... if outdoor work is difficult you can change the procedure For example by making adjustments to the wiring and piping lengths on the inside rather than the outside When using an air conditioner under low outside temperature conditions Outside temp 5 C or lower In COOL mode prepare a duct or wind shield so that it is not affected by the wind Necessary Space for Installation If you need to install t...

Page 12: ...time Use a different diameter joint if the diameters of the connection port and connection piping are different Mount the different diameter joint on the connection port of the outdoor unit CAUTION KEEP IMPORTANT 6 POINTS FOR PIPING WORK 1 Take away dust and moisture inside of the connecting pipes 2 Tighten the connections between pipes and unit 3 Evacuate the air in the connecting pipes using a V...

Page 13: ... the fixed wiring 4 Disconnect the charge hose from the service port then open the valve stem fully using a 4 mm hexagon wrench Hexagon wrench is required Service port cap 4 mm Valve stem cap 5 Tighten the service valve stem cap and service port cap securely CAUTION Use a torque wrench and tighten the nut at the specified torque value 6 Tighten all the caps on the valves securely then perform a ga...

Page 14: ...fied by the matching numbers on the terminal block of the indoor and the outdoor unit 5 Fix the wiring connections for the power source and each indoor unit securely using a cord clamp 6 Attach the terminal cover and the valve cover Stripping Length of connecting cable for outdoor unit 55 5 5 30 1 L 2 3 5 5 30 55 L N Earth screw Earth screw Power cord Connecting cable Unit A Earth screw Earth scre...

Page 15: ... or less Also there is a possibility to misjudge if the indoor temperature becomes too low by cooling operation In that case execute the cooling operation for per room and check if the connection is normal Gas Leak Inspection Refer to the Gas Leak Inspection on page 12 Test run 1 If you perform the test run in summer start running in the cooling mode first to decrease the temperature of the room t...

Page 16: ...lve at the liquid end 9 Make sure that the compound pressure gauge reading is 101 kPa 76 cmHg 10 Close the valve stem of the service valve at the gas end 11 The refrigerants collection operation is finished in maximum 10 minutes After the collection is finished promptly stop the operation of all the indoor unit There are cases that the compressor restarts 12 When you want to start over the operati...

Page 17: ...ture of foreign matter is observed trouble will occur 8 When temporary installation and removal of the air conditioner are repeated such as when leased etc 9 If the type of refrigerator oil of the existing air conditioner is other than the following oil Mineral oil Suniso Freol S MS Synthetic oil alkyl benzene HAB Barrel freeze ester series PVE only of ether series The winding insulation of the co...

Page 18: ...144 9 Moo 5 Bangkadi Industrial Park Tivanon Road Tambol Bangkadi Amphur Muang Pathumthani 12000 Thailand 1116691098 1 ...

Reviews: