11-
9
. How to Simply Judge Whether Outdoor Fan Motor is Good or Bad
1. Symptom
• Outdoor fan motor does not rotate.
• Outdoor fan motor stops within several 10 seconds though it started rotating.
• Outdoor fan motor rotates or does not rotate according to the position where the fan stopped, etc.
Remote controller check code “02 : Outdoor block, 1A : Outdoor fan drive system error”
2. Cause
The following causes are considered when the outdoor fan motor does not normally rotate.
1) Mechanical lock of the outdoor fan motor
2) Winding failure of the outdoor fan motor
3) Position-detect circuit failure inside of the outdoor fan motor
4) Motor drive circuit failure of the outdoor P.C. board
3. How to simply judge whether outdoor fan motor is good or bad
NOTE :
However, GND circuit error inside of the motor may be accepted in some cases when the above check is
performed.
When the fan motor does not become normal even if P.C. board is replaced, replace the outdoor fan motor.
If the resistance value between
1 (Red lead)
– 2 (White lead)
2 (White lead)
– 3 (Black lead)
3 (Black lead)
– 1 (Red lead)
of the connector
(CN300 : Motor winding)
is 20 to 22
Ω
, it is normal.
Turn OFF the breaker.
Fan motor is normal.
Does the fan rotate without trouble
when rotating it with hands?
Disconnect two connectors (CN300) of the
outdoor fan motor from the outdoor P.C. board.
(Outdoor P.C. board error)
Fan motor error
YES
YES
NO
NO
CN300
FILE NO. SVM-12056
–
85
–
Summary of Contents for RAS-18N3AV2-E
Page 108: ...TOSHIBA CARRIER THAILAND CO LTD ...