FILE NO. SVM-12056
A
Die
Pipe
Fig. 10-4-4
CAUTION
<Tightening connection>
Align the centers of the connecting pipes and tighten
the flare nut as far as possible with your fingers. Then
tighten the nut with a spanner and torque wrench as
shown in the figure.
Half union
Flare nut
Externally
threaded side
Internally
threaded side
Use a wrench
to secure.
Use a torque wrench
to secure.
CAUTION
Outer dia. of copper pipe
R410A
∅
6.35
1.5 to 2.0
∅
12.70
2.0 to 2.5
Imperial (wing nut type)
Fig. 10-4-5
(Unit : N·m)
Outer dia.
Tightening torque
of copper pipe
∅
6.35 14 to 18 (1.4 to 1.8 kgf·m)
∅
12.70 50 to 62 (5.0 to 6.2 kgf·m)
.
CAUTION
•
Do not apply excess torque.
•
Otherwise, the nut may crack depending on the
conditions.
<Tightening orque of flare pipe connections>
The operating oressure of R410A is higher than that
of R22 (approx. 1.6 times). It is therefore necessary
to firmly tighten the flare pipe connecting sections
(which connect the indoor and outdoor units) up to the
specified tightening torque. Incorrect connections may
cause not only a gas leakage, but also damage to the
refrigeration cycle.
10-4-
4
. Evacuating
After the piping has been connected to the indoor unit,
you can perform the air purge together at once.
AIR PURGE
Evacuate the air in the connecting pipes and in the
indoor unit using a vacuum pump. Do not use the
refrigerant in the outdoor unit.
For details, see the manual of the vacuum pump.
Fig. 10-4-6
Flare at indoor unit side
Flare at outdoor unit side
<Using a vacuum pump>
Be sure to use a vacuum pump with counter-flow
prevention function so that inside oil of the pump does
not flow backward into pipes of the air conditioner
when the pump stops.
1. Connect the charge hose from the manifold valve to
the service port of the packed valve at gas side.
2. Connect the charge hose to the port of the vacuum
pump.
3. Open fully the low pressure side handle of the
gauge manifold valve.
4. Operate the vacuum pump to start evacuating.
Perform evacuating for about 15 minutes if the piping
length is 20 meters. (15 minutes for 20 meters)
(assuming a pump capacity of 27 liters per minute.)
Then confirm that the compound pressure gauge
reading is
−
101 kPa (
−
76 cmHg).
5. Close the low pressure side valve handle of the
gauge manifold valve.
6. Open fully the valve stem of the packed valves
(both gas and liquid sides).
7. Remove the charging hose from the service port.
8. Securely tighten the caps on the packed valves.
(If oil inside of the vacuum pump enters the air conditioner,
which use R410A, refrigeration cycle trouble may happen.)
–
60
–
Summary of Contents for RAS-18N3AV2-E
Page 108: ...TOSHIBA CARRIER THAILAND CO LTD ...