7-2. Operation Data
FILE NO. SVM-12056
<Cooling>
Standard
Heat exchanger
Indoor
Outdoor
Compressor
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
27/19
35/24
18N3KV2-E
0.9 to 1.1
11 to 13
40 to 42
67
B22N3KV2-E
0.9 to 1.1
11 to 13
41 to 43
77
<Heating>
Tempeature
Standard
Heat exchanger
Indoor
Outdoor
Compressor
condition(°C)
pressure
pipe temp.
fan mode
fan mode
revolution
Indoor
Outdoor
P (MPa)
T1 (°C)
T2 (°C)
(rps)
20/15
7/6
18N3KV2-E
2.5 to 2.6
40 to 42
1 to 3
79
B22N3KV2-E
2.6 to 2.8
42 to 44
0 to 2
84
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 7.5 m