6. Low
temperature
release
protective
control by
temperature
of indoor heat
exchanger
<In cooling/dry operation>
(Prevent-freezing control for indoor heat exchanger)
In cooling/dry operation, the sensor of indoor heat exchanger detects
evaporation temperature and controls the compressor speed so that
temperature of the heat exchanger does not exceed the specifi ed
value.
1
When temperature of the
exchanger drops below
5°C, the compressor speed
is reduced. (P zone)
2
When temperature of the
indoor heat
exchanger rises
exchanger rises in the range
from 6°C to under 7°C, the
compressor speed is kept.
(Q zone)
3
When temperature of the
indoor heat
exchanger rises
to 7°C or higher, the
capacity control operation
returns to the usual control
in cooling operation.
(R zone)
7˚C
6˚C
5˚C
R
Q
P
Usual cooling capacity control
Reduction of compressor speed
Indoor heat e
xchanger temper
ature
When the value is
in Q zone, the
compressor speed
is kept.
Item
Operation flow and applicable data, etc.
Description
FILE NO. SVM-15058
- 33 -