Toshiba RAS-10G2AVP Series Installation Manual Download Page 4

2

WARNING

•  Installation work must be requested from the supplying retail dealership. Self-installation may cause water leakage, electrical shock, or 

fi

 re as a result 

of improper installation.

• Speci

fi

 ed tools and pipe parts for model R410A are required, and installation work must be done in accordance with the manual. HFC type refrigerant 

R410A has 1.6 times more pressure than that of conventional refrigerant (R22). Use the speci

fi

 ed pipe parts, and ensure correct installation, otherwise 

damage and/or injury may be caused. At the same time, water leakage, electrical shock, and 

fi

 re may occur.

•  Be sure to install the unit in a place which can suf

fi

 ciently bear its weight. If the load bearing of the unit is not enough, or installation of the unit is 

improper, the unit may fall and result in injury.

•  Electrical work must be performed by a quali

fi

 ed supplying retail dealership in accordance with the code governing such installation work, internal 

wiring regulations, and the manual. A dedicated circuit and the rated voltage must be used. Insuf

fi

 cient power supply or improper installation may 

cause electrical shock or 

fi

 re.

•  Use a cabtyre cable to connect wires in the indoor/outdoor units. Midway connection, stranded wire, and single-wire connections are not allowed.
  Improper connection or 

fi

 xing may cause a 

fi

 re.

•  Wiring between the indoor unit and outdoor units must be well shaped so that the cover can be 

fi

 rmly placed. Improper cover installation may cause 

increased heat, 

fi

 re, or electrical shock at the terminal area.

•  Be sure to use only approved accessories or the speci

fi

 ed parts. Failure to do so may cause the unit to fall, water leakage, 

fi

 re or electrical shock.

•  After the installation work, ensure that there is no leakage of refrigerant gas. If the refrigerant gas leaks out of the pipe into the room and is heated by 

fi

 re or something else from a fan heater, stove or gas range, it causes generation of poisonous gas.

•  Make sure the equipment is properly earthed. Do not connect the earth wire to a gas pipe, water pipe, lightning conductor, or telephone earth wire.
  Improper earth work may be the cause of electrical shock.
•  Do not install the unit where 

fl

 ammable gas may leak. If there is any gas leakage or accumulation around the unit, it can cause a 

fi

 re.

•  Do not select a location for installation where there may be excessive water or humidity, such as a bathroom. Deterioration of insulation may cause 

electrical shock or 

fi

 re.

•  Installation work must be performed following the instructions in this installation manual. Improper installation may cause water leakage, electrical 

shock or 

fi

 re. Check the following items before operating the unit.

  -  Be sure that the pipe connection is well placed and there are no leaks.
  -  Check that the service valve is open. If the service valve is closed, it may cause overpressure and result in compressor damage. At the same time, if 

there is a leak in the connection part, it may cause air suction and overpressure, resulting burst or injury.

•  In pump down operations, ensure to perform the following procedures.
  -  Do not inject air into the refrigeration cycle.
  -  Be sure to close both service valves and stop the compressor before removing the refrigerant pipe. If removing the refrigerant pipe while the 

compressor is operating with the service valves opened, it may cause to air absorbed and abnormal high pressure inside the refrigeration cycle and 
resulting burst or injury.

•  Do not modify the power cable, connect the cable midway, or use a multiple outlet extension cable. Doing so may cause contact failure, insulation 

failure, or excess current, resulting in 

fi

 re or electrical shock.

•  Do not use any refrigerant different from the one speci

fi

 ed for complement or replacement. Otherwise, abnormally high pressure may be generated in 

the refrigeration cycle, which may result in a failure or explosion of the product or an injury to your body.

•  Be sure to comply with local regulations/codes when running the wire from the outdoor unit to the indoor unit. (Size of wire and wiring method etc.)
•  Places where iron or other metal dust is present. If iron or other metal dust adheres to or collects on the interior of the air conditioner, it may 

spontaneously combust and start a 

fi

 re.

•  If you detect any damage, do not install the unit. Contact your supplying dealer immediately.
•  Never modify this unit by removing any of the safety guards.
•  Do not install in a place which cannot bear the weight of the unit. Personal injury and property damage can result if the unit falls.

CAUTION

•  Please read this installation manual carefully before installing the unit. It contains further important instructions for proper installation.
•  Exposure of unit to water or other moisture before installation could result in electric shock. Do not store it in a wet basement or expose to rain or water.
•  After unpacking the unit, examine it carefully for possible damage.
•  Do not install in a place that can increase the vibration of the unit. Do not install in a place that can amplify the noise level of the unit or where noise and 

discharged air might disturb neighbors.

•  This appliance must be connected to the main power supply by means of a circuit breaker depending on the place where the unit is installed. Failure to do 

so may cause electrical shock.

•  Follow the instructions in this installation manual to arrange the drain pipe for proper drainage from the unit. Ensure that drained water is discharged.
  Improper drainage can result in water leakage, causing water damage to furniture.
• Tighten the 

fl

 are nut with a torque wrench using the prescribed method. Do not apply excess torque. Otherwise, the nut may crack after a long period of 

usage and it may cause the leakage of refrigerant.

•  Wear gloves (heavy gloves such as cotton gloves) for installation work. Failure to do so may cause personal injury when handling parts with sharp edges.
•  Do not touch the air intake section or the aluminum 

fi

 ns of the outdoor unit. It may cause injury.

•  Do not install the outdoor unit in a place which can be a nest for small animals. Small animals could enter and contact internal electrical parts, causing a 

failure or 

fi

 re.

•  Request the user to keep the place around the unit tidy and clean.
•  Make sure to conduct a trial operation after the installation work, and explain how to use and maintain the unit to the customer in accordance with the 

manual. Ask the customer to keep the operation manual along with the installation manual.

REQUIREMENT OF REPORT TO THE LOCAL POWER SUPPLIER

Please make absolutely sure that the installation of this appliance is reported to the local power supplier before installation. If you experience any problems 
or if the installation is not accepted by the supplier, the service agency will take adequate countermeasures.

1115751104-EN.indd   2

1115751104-EN.indd   2

5/26/2557 BE   10:45 AM

5/26/2557 BE   10:45 AM

Summary of Contents for RAS-10G2AVP Series

Page 1: ...VP Series RAS 16G2KVP Series Outdoor unit RAS 10G2AVP Series RAS 13G2AVP Series RAS 16G2AVP Series AIR CONDITIONER SPLIT TYPE INSTALLATION MANUAL 1115751104 1115751104 EN indd 1 1115751104 EN indd 1 5 26 2557 BE 10 45 AM 5 26 2557 BE 10 45 AM ...

Page 2: ... OUTDOOR UNIT 6 Installation Place 6 Refrigerant Piping Connection 6 Evacuating 7 ELECTRICAL WORKS 8 Wiring Connection 8 Power Supply and Connecting Cable Connection 9 Power supply input Wiring Diagram 10 Wiring between DRED Demand response enabling device and Outdoor Unit 11 Connection procedure 11 Outdoor unit preparation 12 OTHERS 13 Gas Leak Test 13 Remote Control A B Selection 13 Test Operati...

Page 3: ...T IN ANOTHER PLACE AGAIN BE VERY CAREFUL NOT TO GET THE SPECIFIED REFRIGERANT R410A WITH ANY OTHER GASEOUS BODY INTO THE REFRIGERATION CYCLE IF AIR OR ANY OTHER GAS IS MIXED IN THE REFRIGERANT THE GAS PRESSURE IN THE REFRIGERATION CYCLE BECOMES ABNORMALLY HIGH AND IT RESULTINGLY CAUSES BURST OF THE PIPE AND INJURIES ON PERSONS IN THE EVENT THAT THE REFRIGERANT GAS LEAKS OUT OF THE PIPE DURING THE ...

Page 4: ...bsorbed and abnormal high pressure inside the refrigeration cycle and resulting burst or injury Do not modify the power cable connect the cable midway or use a multiple outlet extension cable Doing so may cause contact failure insulation failure or excess current resulting in fire or electrical shock Do not use any refrigerant different from the one specified for complement or replacement Otherwis...

Page 5: ...or the rear left and left piping Wall Make sure to run the drain hose sloped downward Do not allow the drain hose to get slack Cut the piping hole sloped slightly The auxiliary piping can be connected to the left rear left rear right right bottom right or bottom left Right Rear right Bottom right Rear left Bottom left Left 1 Batteries Flat head wood screw Remote control holder Vinyl tape Apply aft...

Page 6: ...ted in the below figure 3 Install the installation plate horizontally in the wall When installing the installation plate with a mounting screw do not use the anchor bolt holes Otherwise the unit may fall down and result in personal injury and property damage 1 After determining the pipe hole position on the mounting plate drill the pipe hole Ø65 mm at a slight downward slant to the outdoor side A ...

Page 7: ...cation causes deterioration and drain leakage of the plug No gap Insert a hexagon wrench 4 mm 326 mm 283 mm 43 mm 80 Liquid side Gas side To the forefront of flare Outward form of indoor unit R 30 mm Use polisin polyethylene core or the like for bending pipe Use the handle of screwdriver etc Slit Cap Slit NOTE If the pipe is bent incorrectly the indoor unit may unstably be set on the wall After pa...

Page 8: ...w which forms on the back of the indoor unit to the drain pan Therefore do not store the power cord and other parts at a height above the drain guide CAUTION OUTDOOR UNIT OUTDOOR UNIT Installation Place A place which provides the spaces around the outdoor unit as shown in the diagram A place which can bear the weight of the outdoor unit and does not allow an increase in noise level and vibration A...

Page 9: ...10A refrigeration cycle trouble may result 1 Connect the charge hose from the manifold valve to the service port of the packed valve at gas side 2 Connect the charge hose to the port of the vacuum pump 3 Open fully the low pressure side handle of the gauge manifold valve 4 Operate the vacuum pump to start evacuating Perform evacuating for about 15 minutes if the piping length is 25 meters 15 minut...

Page 10: ... with the cord clamp 8 Fix the terminal cover and attach front panel to the indoor unit Cable about 20 cm Front panel Terminals block Main panel Terminal cover 1 Remove the valve cover from the outdoor unit 2 Connect the cable to the terminals as identified with their respective matched numbers on the terminal block of indoor and outdoor unit 3 When connecting the cable to the outdoor unit termina...

Page 11: ...Stripping length of the connecting cable 3 Connecting cable 50 mm 45 mm 10 mm Earth line about 20 cm Power Supply Input at Outdoor Unit Terminal Block Optional Indoor Unit Outdoor Unit Connecting CABLE Connecting cable connect to terminal block 3 Connecting cable connect to terminal block L N Stripping length of the connecting cable 3 N L Connecting cable 50 mm 90 mm 10 mm Earth line about 20 cm 4...

Page 12: ...t burn out 8 Incorrect or incomplete wiring is carried out it will cause an ignition or smoke 9 This product can be connected to main power supply Connection to fixed wiring A switch which disconnects all poles and has a contact separation at least 3mm must be incorporated in the fixed wiring Power supply input Wiring Diagram Indoor Terminal Block Power supply input Outdoor Terminal Block Indoor T...

Page 13: ...ectric shock fire or refrigerant leak Wear heavy gloves during the installation work to avoid injury CAUTION Connection procedure This air conditioner complies with AS NZS 4755 3 1 DRM available DRM1 DRM2 DRM3 The terminal block meets ELV requirements COM DRM1 DRM2 DRM3 COM DRM1 DRM2 DRM3 CN01 WHI CN102 IC103 C100 DB100 C103 D101 COM DRM1 DRM2 DRM3 10 30 COM DRM1 DRM2 DRM3 Stripping length for DRE...

Page 14: ...Front cabinet 5 Left side of front cabinet is inserted into Left side cabinet remove by lift up the front cabinet 6 Slide the DRI cover to open for wire connection 7 Connect DRED wires to the terminal of DRM 8 Reassembly by reverse process Upper cabinet Water proof cover Valve cover 5 4 Demand response interface DRI 6 Demand response interface DRI DRI cover Outdoor unit preparation 3 1115751104 EN...

Page 15: ...nt two rooms if operating a unit two units may receive the remote control signal simultaneously and operate In this case the operation can be preserved by setting either one remote control to B setting Both are set to A setting in factory shipment The remote control signal is not received when the settings of indoor unit and remote control are different There is no relation between A setting B set...

Page 16: ...1115751104 1115751104 EN indd 14 1115751104 EN indd 14 5 26 2557 BE 10 45 AM 5 26 2557 BE 10 45 AM ...

Reviews: