background image

 

QX7

 

APPLICATION GUIDELINE 1.2 

 

*

 

For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192  

 

Unlocking VI/II Input Rev. 3 

Introduction 

This feature allows you to correct a glitch when the QX7 drive is not responding to VI/II 

input signal. This should be used on drives prior to Rev. 4. (See software revision 

document). 

Programming  

 

Keystroke 

LED Display 

Press Setup/program/monitor key 

Setup 

Press Setup/program/monitor key 

Program 
Search 

Down arrow 11 times 

Program 
Input Terminals 

Read/Write 

F Terminal   
Forward (NO) 

Up arrow 6 times 

S3 Terminal 
Set Speed 3 (NO) 

Read/Write 

S3 Terminal  *Flashing* 
Set Speed 3 (NO) 

Down arrow 14 times 

S3 Terminal  *Flashing* 
Unassigned (NO) 

Read/Write 

S3 Terminal 
Unassigned (NO) 

Setup/Program/Monitor  

3 times 

Output Frequency 
                   0.0Hz 

 
Notes 
 

Re-check to assure all parameters are set properly. 

 