Q9 Plus Bypass ASD/Bypass Box Installation and Operation Manual
43
Cable/Terminal Specifications
The following ratings are guidelines and shall not be the sole determining factor of the lug or wire size
used with the
Q9 Plus Bypass ASD/Q9 Plus Bypass Box
. Application-specific variables, wire
insulation type, and conductor material are but a few of the considerations necessary when selecting the
actual lug and wire type to be used.
As a minimum, the installation of the ASD shall conform to the requirements of the
NEC Article 110
and
Article 430
, the
Occupational Safety and Health Administration
requirements, and to any other
local and regional industry codes and standards.
Note:
Use only 75° C copper wire/cable for motor and power connections.
Table 6. Q9 Plus Bypass ASD/Q9 Plus Bypass Box 230- and 460-Volt Drive Cable/Terminal
Specifications.
Model No.
MCP
Rating
(Amps)
Typical Wire/Cable Size
Lug Size/Wire Capacity
AWG/kcmil
Input/Output
Power
TB1
TB2 – TB6
ASD
Input/Output
OL Relay Output
Circuit Breaker
Input
Q9+2015
7
14
18
(2-core shield)
20
(3-core shield)
14 – 1/0
8 – 18
14 – 1/0
Q9+2025
15
Q9+2035
12
Q9+2055
30
10
Q9+2080
8
12
–
8
Q9+2110
50
10
–
4
10 – 1/0
Q9+2160
75
6
8
–
2
Q9+2220
4
Q9+2270
100
2
4
–
1/0
Q9+2330
250
14 – 2/0
4
–
4/0
Q9+2400
1/0
BYP2-100
2
6
– 3/0
BYP2-125
1/0
2
–
300
Q9+4015
7
14
18
(2-core shield)
20
(3-core shield)
14 – 1/0
8
–
18
14
–
1/0
Q9+4025
Q9+4035
Q9+4055
15
Q9+4080
12
Q9+4110
30
10
12
–
8
Q9+4160
8
10
–
4
Q9+4220
50
Q9+4270
6
8
–
2
10
–
1/0
Q9+4330
Q9+4400
75
4
4
–
1/0
Q9+4500