Q9 Plus Bypass ASD/Bypass Box Installation and Operation Manual
19
Overload Circuit Protector Adjustment and Setting
The trip threshold of the
OCP
is set to the lowest setting when the product ships from the factory. The
OCP
setting should allow for the high inrush current of startup and the short-time overload current of
high-inertia loads but not be set so high as to provide inadequate overcurrent protection. The
OCP
should be set to a level that is just above the maximum level of the application’s normal operating
requirements.
A motor starter is recommended for larger motors.
Overload settings are application-specific and should be set and/or adjusted by
Qualified Personnel
ONLY
(see
Figure 4. Motor OCP Adjustment and OCP Contactor.
The Normally Open (NO) and Normally Closed (NC)
contacts remain in their normal states during normal
operation. Both contacts change states during an overload trip.
The contacts may be used with ancillary circuitry to
annunciate an overload trip or to control other system
features.
Set to minimum at the factory.
Application-specific
adjustment is required.