P9 ASD Installation and Operation Manual
Cable/Terminal/Torque Specifications
Installation should conform to the
NEC
Article 110 (NEC
) (Requirements for Electrical Installations), all
regulations of the Occupational Safety and Health Administration, and any other applicable national,
regional, or industry codes and standards.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the P9 ASD. Application-specific applicables, wire insulation
type, conductor material, and local and regional regulations are but a few of the
considerations when selecting the actual lug and wire type to be used with the P9 ASD.
Note:
Cable/Terminal specifications are based on the rated current of the P9 ASD and
Do Not
include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
For further installation information, see the section titled
Installation and Connections on pg. 14
Note:
(*) Indicates that the item is one of a set of two parallel cables.
Table 21. 230-Volt P9 ASD Cable/Terminal/Torque Specifications.
Model
Number
VT130P9U
MCP Rating
(Amps)
Wire/Cable Size
Lug Size Range
Terminal
Board
Torque
AWG or kcmil
Input/Output Power
Wire-Size/Lug-Capacity for
Input/Output Power
TB1 – 4
Terminals
3Ø-Input 3Ø-Output
Recommended Maximum
3Ø-Input
3Ø-Output
In-Lbs./Nm
2010
15
14
10
14 to 8
20
(3-core shield)
Torque to 5.3/0.6
11.5/1.3
2015
2025
2035
30
2055
10
2080
50
8
8
12 to 8
17.7/2.0
2110
2160
75
6
3
8 to 3
21/2.4
2220
100
4
2270
125
3
2330
150
2
2
12 to 1/0
4 to 1/0
50/5.7
53/6
2400
175
1/0
4/0
6 to 250
2 to 300
275/31
168/19
2500
200
2/0
2600
250
3/0
2750
300
4/0
210K
400
*3/0
6 to 250
275/31
212K
500
*250
*250