F-GAS label
This product contains
fl
uorinated greenhouse gases
• Chemical Name of Gas
R410A
• Global Warming Potential (GWP) of Gas
2088 (ex.R410A ref.AR4)
CAUTION
1. Stick the enclosed refrigerant label adjacent to the service ports for charging or recovering location and where
possible adjacent to existing nameplates or product information label.
2. Clearly write the charged refrigerant quantity on the refrigerant label using indelible ink. Then, place the
included transparent protective sheet over the label to prevent the writing from rubbing off.
3. Prevent emission of the contained
fl
uorinated greenhouse gas. Ensure that the
fl
uorinated greenhouse gas is
never vented to the atmosphere during installation, service or disposal. When any leakage of the contained
fl
uorinated greenhouse gas is detected, the leak shall be stopped and repaired as soon as possible.
4. Only quali
fi
ed service personnel are allowed to access and service this product.
5. Any handling of the
fl
uorinated greenhouse gas in this product, such as when moving the product or recharging
the gas, shall comply under (EU) Regulation No. 517/2014 on certain
fl
uorinated greenhouse gases and any
relevant local legislation.
6. Periodical inspections for refrigerant leaks may be required depending on European or local legislation.
7. Contact dealers, installers, etc., for any questions.
Heat insulation for pipe
• Apply heat insulation of pipe separately at the liquid, gas, and balance sides.
• Be sure to use thermal insulator resistant up to 120°C or higher for pipes at the gas side.
Finishing after connecting pipes
• After piping connection work has been
fi
nished, cover the opening of the piping/wiring panel with the piping
cover, or
fi
ll silicon or putty into the space between the pipes.
• In case of drawing-out the pipes downward or sideward, also close the openings of the base plate and the side
plate.
• Under the opened condition, a problem may be caused due to the entering of water or dust.
When using the piping cover
When not using the piping cover
Piping/wiring panel
Drawing-out sideward
Drawing-out
frontward
Drawing-out
downward
Close the opening with the
pipe cover.
Piping/wiring panel
Drawing-out sideward
Fill silicon or putty into the
periphery of the pipes.
Drawing-out
downward
Drawing-out
frontward
¿
Pipe holding bracket
Attach pipe holding brackets following the table below.
Diameter of pipe (mm)
Interval
Ø15.9 - Ø19.1
2m
Ø22.2 - Ø41.3
3m