– 84 –
NO.
Item
Specification outline
Remarks
8 Release valve
control
1. SV2 gas balance control
This control function is aimed at achieving gas balance by opening SV2 while
compressors are turned off so as to reduce their startup load the next time they
are turned on. It is individually performed by the header outdoor unit and each
follower outdoor unit.
1) Control conditions
• In cooling, compressors have been turned off.
• In heating, the header unit has been shut down.
2) Control details
• The control point is changed according to
Δ
P (Pd pressure - Ps pressure)
registered just before the compressors were turned off.
• When
Δ
P
≥
P1, SV2 is opened. When this results in
Δ
P < P2, SV2 is closed.
• When
Δ
P < P1, SV2 is closed.
Control points
for Pd
pressure
P1, P2
Heating
Cooling
(Unit: MPa)
Header unit compressors Header unit compressors Header unit compressors
OFF
OFF
ON
P1
P2
P1
P2
P1
P2
1.3
1.1
Header unit
1.3
1.1
—
—
1.3
1.1
Follower unit
1.3
1.1
0.5
0.4
2. SV2 high pressure release control
This control function is aimed at mitigating pressure rise while a compressor is in
operation at low speeds.
1) Control conditions
• In case of single heating, single cooling, collective heating or collective cooling
is operating
• In case that a header unit singly operates a compressor
2) Control details
• When Pd pressure becomes 3.4 MPa, SV2 is opened.
• When Pd pressure becomes 2.8 MPa, SV2 is closed.
3) Termination conditions
• Shutdown, thermo OFF, defrosting operation.
• The number of header unit compressors in operation increases to two or more.
• At least one follower unit compressor is turned on.
3. SV2 low pressure release control
This control function is aimed at preventing a rapid fall in pressure during transient
operation. It is individually performed by the header outdoor unit and each follower
outdoor unit.
The control is always provided except during periods of stoppage or thermo OFF.
1) Control details
• When Ps pressure becomes
≤
0.16 MPa, SV2 is opened.
• When Ps pressure becomes > 0.20 MPa, SV2 is closed.
4. SV41, 42, 43 low pressure release control
This control function is aimed at providing low pressure protection, and is
individually performed by the header unit and each follower unit.
The control takes place during defrost operation, heating operation, collecting
heating, collective cooling and single cooling operation.
1) Control details (heating)
When Ps pressure becomes 0.1 MPa, SV41, 42 and 43 are opened; when Ps
pressure becomes 0.15 MPa, SV41, 42 and 43 are closed.
2) Control details (cooling)
When Ps pressure and Pd pressure become 0.14 MPa and 1.7 MPa,
respectively, SV41 and 42 are opened; when Ps pressure and Pd pressure
become 0.19 MPa and 2.2 MPa, respectively, SV41 and 42 are closed.
5. SV6 valve clean bypass control
This control is provided for controlling liquid refrigerant bypass to control discharge
temperature-up or temperature inside of the compressor. It works during single
cooling, single heating, collective cooling, collective heating, collective heating and
defrost operation.
1) Control contents (Single cooling)
When TD temperature
≥
95°C and compression ratio
≥
3.0, turn SV6 to ON, and
when TD temperature
≤
83°C or compression ratio
≥
2.0, turn SV6 to OFF.
2) Control contents (Other operation)
When TD temperature
≥
95°C and compression ratio
≥
4.2, turn SV6 to ON, and
when TD temperature
≤
83°C or compression ratio
≥
3.2, turn SV6 to OFF.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...