– 79 –
5-2. Outdoor Unit
NO.
Item
Specification outline
Remarks
1 Pulse motor
valve (PMV)
control
1. PMV1, 2 control (PMV1 and 2)
1) During air conditioner operation, the pulse count of a PMV (pulse motor valve) is
controlled between 90 and 1000.
2) During single cooling, the PMV opening is controlled on the basis of
measurements provided by the TL temperature sensor and the Pd pressure
sensor (under cool control).
3) During single heating, the PMV opening is controlled on the basis of
measurements provided by the TS and TD temperature sensors and the PS
pressure sensor (super heat control).\
4) PMVs are fully closed when the air conditioner is in thermo OFF state or upon
being turned off normally or shut down due to an abnormality.
• During single
heating, collective
heating, PMV
control may be
provided with
PMV1 alone,
operated at 45
pulses
(minimum), with
PMV2 turned off.
PMV 1
PMV 2
1000
550
500
90
45
Minimum
Maximum
Opening of PMV1, 2
MAX
1000
PMV1, 2 opening
Controlled between
90 and 1000 pulses
– 10
SH control
2
Cooling-heating demand capacity difference (HP)
0
MAX
500
PMV4 opening
– 2
0
10
Cooling-heating demand capacity difference (HP)
Collective cooling operation area
Collective heating operation area
0
45
2. PMV4 control
1) PMV4 (Pulse Motor Valve) is controlled between 0 and 500 pulses at collective
cooling / heating operation.
2) PMV4 opening is controlled according to the demand capacity difference (HP)
between cooling and heating operation.
3) PMVs are fully closed when the air conditioner is in thermo OFF state or upon
being turned off normally or shut down due to an abnormality.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...