– 289 –
13-2-5. Fan IPDU P.C. Board (MCC-1610) Replacement Procedure
Replacement steps:
(1) Turn off the power supply of the outdoor unit and allow at least one minute for the capacitor to discharge.
Confirm that the light of the LED (D640) fades away.
(2) Remove all the connectors and the fast-on terminals (
1
) connected to the FAN IPDU. (Remove the
connectors and fast-on terminals by pulling the connector body. Do not pull the wire).
(3) Remove all the five screws (
2
) which secures the FAN IPDU to the Heat sink.
(These screws are to be re-used after procedure.)
(4) Remove the Fan IPDU from the three PCB Mounts (
3
).
FAN IPDU
(MCC-1610)
LED
(D640)
3
3
Screw
2
2
2
2
2
Fast-on terminal
1
RED
lead wire
Fast-on terminal
1
WHITE
lead wire
Fast-on terminal
1
BLACK
lead wire
Push this part to the
direction of the arrow.
And remove the PCB.
PCB Mounts
3
Heat Sink
Sub Heat Sink
Remove the PCB
IC701
DB510
Q590
DB509
(5) Confirm that no dirt or damage is on the sub heat sink. As it can reduce the heat transfer efficiency, and
cause a breakdown.
(6) Align the PCB mount holes on the PCB with the PCB mounts, and fix the FAN IPDU to the outdoor control
unit by clipping the PCB into the PCB mounts (
3
).
(7) Screw the FAN IPDU to the heat sink by the five screws that were removed in step (3). If the screws are
loose, the effected component will generate heat, and cause in to breakdown. Do not use an electric driver
or an air driver, as it can cause component damage. The torque of 5 screws (IC701, DB509, DB510 and
Q590) is “0.55N•m”.
(8) Re-connect the connectors and fast-on terminals(
1
). Be sure that all the connectors and the fast-on
terminals are connected correctly and securely inserted.
(9) If the components on the PCB were bent during this procedure, straighten them so they do not to touch
other parts.
(10) Install the cover, then turn on the supply. Check the operation.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...