– 279 –
Procedure 1: Reading Setting Data from EEPROM
(Read the setting data from EEPROM, including both the factory settings and any modifications made to them
on site.)
1
Push the
TEST
+
SET
+
CL
buttons simultaneously and hold for at least 4 seconds.
1
(This
number corresponds to the same number shown on the Remote Controller Operation
Diagram.)
* In the case of group control, the unit No. displayed first is the indoor unit No. of the header unit.
At the same time, the CODE No. (DN code) 10 is displayed, and the fan of the selected indoor unit
comes on, with the louver swinging, depending on the model.
2
Each time the
UNIT LOUVER
button (left side of the button.) is pushed, one of the indoor unit No.
under group control is displayed in turn.
2
* The fan of the selected indoor unit comes on, with the flaps swinging, depending on the model.
3
The
TEMP
button allows you to move the CODE No. (DN code) up/down by one place.
3
4
First, change the CODE No. (DN code) from 10 to 01. (To set filter sign lighting time)
Jot down the setting data displayed.
5
Change the CODE No. (DN code) using the
TEMP
button.
Again, jot down the setting data displayed.
6
Repeat step 5 until all the setting data has been jotted down. (See the CODE No. list.)
* CODE No. (DN code) go from 01 to FF with a few gaps along the way.
7
When finished, push the
TEST
button to bring the system back to normal off state.
6
(It takes the system about 1 minute to become responsive to remote controller operation.)
CODE No. (DN code) necessary at minimum
DN
Contents
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor address
14
Group address
SET DATA
R.C.
No.
UNIT No.
CODE No.
TEMP.
ON / OFF
PROGRAM DAY
TIME
SAVE
3, 5
7
1
6
2
4
FILTER UP/DN
SCHEDULE
FAN
MODE
VENT
FLT.RESET TEST
SET CL
SWING/FIX
UNIT
LOUVER
<Fig. 2 RBC-AMS41E>
TEMP.
ON / OFF
SETTING
SETDATA
UNIT
CODE
No.
No.
R.C.
No.
SET
TIME
TIMER SET
TEST
FILTER
RESET
CL
FAN
SAVE
SWING/FIX
VENT
MODE
UNIT LOUVER
3, 5
7
1
6
2
4
<Fig. 1 RBC-AMT32E>
The type and capacity of the indoor unit are necessary for fan speed setting.
Remote Controller Operation Diagram
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...