– 250 –
9-3. Backup Setup for Outdoor Unit
Outline
In this model, setup of the backup operation is available in either the header unit or the follower unit in a
situation where the outdoor units are defective. In a system in which two or more outdoor units are connected,
carry out the backup operation on the outdoor unit if the error modes described below occur.
• Compressor error (Rare short error or when one compressor cannot operate, etc.)
• Pressure sensor (Pd, Ps) / Temperature sensor (TD1, TD2, TD3, TS1, TS2, TE1, TE2, TK1, TK2, TK3, TK4,
TK5, TL) error
Note only one outdoor unit within a given system can be subjected to the backup procedure.
Procedure
(1) Turn off the main power supplies to all the units connected to the system.
[Set up procedure for the malfunctioning outdoor unit]
(The following work is common to the header unit and follower units in the system.)
(2) Set the DIP switches of SW06, provided on the interface P.C. board of the outdoor unit with the faulty
compressor, as shown in the table below.
Three-compressor model
SW06
SW06
Bit 1
Bit 2
Bit 3
Bit 4
Bit 1
Bit 2
Bit 3
Bit 4
Factory default setting
Outdoor unit backup
Two-compressor model
Factory default setting
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
OFF
OFF
OFF
OFF
Outdoor unit backup
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
SW06
SW07
SW09
SW10
SW11
SW12
1
2
3
4
1
2
3
4
SW16
SW17
SW13
SW14
(3) When there is leakage of outdoor PMV (does not close) or a trouble, close the liquid valve service valves fully.
(4) Turn on the power supply to all the units connected to the system.
When a trouble due to insufficient insulation, etc. occurred, remove in advance lead wire of the compressor.
This is the end of compressor backup operation setting.
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...