– 226 –
(1) Display of System Information (Displayed on Header Outdoor Unit Only)
F
G
A
D
U2
U1
U3
U4
Dp
B
E
C
Display section A
Display section B
Outdoor unit No.
SW01
SW02
SW03
Display detail
A
Unused
B
A
2
System capacity
[...8]~[42]:8 to 42 HP
B [HP]
A
3
No. of outdoor units
[...1]~[...3]:1 to 3
B [...P]
A
4
No. of indoor units connected /
No. of units with cooling thermo ON
[...0.]~[48.]:0 to 48 (No. of units connected)
B [C...0]~[C48]:0 to 48 (No. of units with cooling thermo ON)
A
5
No. of indoor units connected /
No. of units with heating thermo ON
[...0.]~[48.]:0 to 48 (No. of units connected)
B [H...0]~[H48]:0 to 48 (No. of units with heating thermo ON)
A
7
Release control
Normal: [r. ...], During release control: [r.1]
B —
8
Oil equalization control
Normal: [oiL-0]
During oil equalization control: [oiL-1]
A
6
Amount of compressor command
correction
Value displayed in hexadecimal format
B
A
9
Oil equalization request
Displayed through LED segment lighting pattern
If element F shown on sketch at right turned on:
Header unit oil equalization request
If element C shown on sketch at right turned on:
Follower unit oil equalization request
B
A
10
Refrigerant/oil recovery operation
Oil recovery in cooling: [C1], Normal: [C ...]
B Refrigerant recovery in heating: [H1], Normal: [H ...]
A
11
Automatic addressing
[Ad]
B During automatic addressing: [... FF], Normal: [... ... ...]
A
16
—
—
B —
A
12
Power pick-cut
[dU]
14
Optional control
(BUS line input)
Same as above
B Normal: [... ... ...], During 50-90% capacity operation: [_50-_90]
While control is based on BUS line input: [E50-E90]
13
3
1
Optional control (P.C. board input)
Displays optional control status
A
V
Operation mode selection: During priority heating (normal)
h.
∗
.
∗
.
∗
.
∗
.
Heating only
H.
∗
.
∗
.
∗
.
∗
.
Cooling only
C.
∗
.
∗
.
∗
.
∗
.
Start input
∗
.1.
External master ON/OFF: Normal
∗
.....
∗
.
∗
.
∗
.
∗
.
∗
.
∗
.
Stop input
∗
.0.
∗
.
∗
.
∗
.
Start input
∗
.
∗
.
Night operation: Normal
∗
.
∗
.
1.
∗
.
∗
.
....
∗
.
∗
.
Start input
∗
.
∗
.
Snowfall operation: Normal
∗
.
∗
.
∗
.1.
∗
.
∗
....
∗
.
Unused
15
1
AMP Air Conditioning
www.ampair.co.uk | [email protected]
Summary of Contents for MMY-MAP0804FT7(Z)
Page 24: ... 24 Models MMY MAP1204 MAP1404 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 33: ... 33 Models MMD AP0724H and AP0964H AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 47: ... 47 RBM Y2803FE AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 236: ... 236 AMP Air Conditioning www ampair co uk sales ampair co uk ...
Page 238: ... 238 AMP Air Conditioning www ampair co uk sales ampair co uk ...